| 2021-01-04 13:32:36 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT |
| | FROM UTILITY. |
| | |
| | E3404.2INTERRUPTING RATING. |
| | |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS |
| | SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 |
| | AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| | LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT |
| | LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) |
| | |
| | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED |
| | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24 & FBC RE E3606.4 |
| | |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | 3. R404.1LIGHTING EQUIPMENT (MANDATORY). |
| | NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY |
| | HIGH-EFFICACY LAMPS. |
| | EXCEPTION: LOW-VOLTAGE LIGHTING. |
| | A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| | |
| | 4. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |