2021-01-04 10:15:43PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: GUEST CASITA
  
 1. SERVICE DISCONNET REQUIRED.
  
 E3601.6.2SERVICE DISCONNECT LOCATION.
 THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR INSIDE NEAREST THE POINT OF ENTRANCE OF THE
 SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL
 NOT BE INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE
 ACCESS TO THE DISCONNECT SERVING THE DWELLING UNIT IN
 WHICH THEY RESIDE. [230.70(A)(1), 230.72(C)]
  
 E3601.7MAXIMUM NUMBER OF DISCONNECTS.
 THE SERVICE DISCONNECTING MEANS SHALL CONSIST OF NOT
 MORE THAN SIX SWITCHES OR SIX CIRCUIT BREAKERS MOUNTED
 IN A SINGLE ENCLOSURE OR IN A GROUP OF SEPARATE
 ENCLOSURES. [230.71(A)]
  
  
2020-12-21 15:26:58NEW GUEST CASITA (SEE DRAWINGS UNDER MAIN HOUSE PERMIT
 #20100209).
  
  
  
  