| 2021-01-04 10:15:43 | PLAN REVIEW / ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2014 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | RE: GUEST CASITA | | | | | | 1. SERVICE DISCONNET REQUIRED. | | | | | | E3601.6.2SERVICE DISCONNECT LOCATION. | | | THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A | | | READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A | | | BUILDING OR INSIDE NEAREST THE POINT OF ENTRANCE OF THE | | | SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL | | | NOT BE INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE | | | ACCESS TO THE DISCONNECT SERVING THE DWELLING UNIT IN | | | WHICH THEY RESIDE. [230.70(A)(1), 230.72(C)] | | | | | | E3601.7MAXIMUM NUMBER OF DISCONNECTS. | | | THE SERVICE DISCONNECTING MEANS SHALL CONSIST OF NOT | | | MORE THAN SIX SWITCHES OR SIX CIRCUIT BREAKERS MOUNTED | | | IN A SINGLE ENCLOSURE OR IN A GROUP OF SEPARATE | | | ENCLOSURES. [230.71(A)] | | | | | | | | 2020-12-21 15:26:58 | NEW GUEST CASITA (SEE DRAWINGS UNDER MAIN HOUSE PERMIT | | | #20100209). | | | | | | | | | | | | |
|