| Date |
Text |
| 2021-03-19 13:19:45 | IT APPEARS THAT NONE OF THE EXISTING COMMENTS HAVE BEEN |
| | ADDRESSED ON THIS RESUBMITTAL. |
| | |
| | 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 3) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU |
| | LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). |
| | 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER) TO THE MOST REMOTE OUTLET/ REGULATOR IN THE |
| | BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS |
| | SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, |
| | G2413.4.2. NOTE: EXISTING PLANS ON FILE WITH THE CITY |
| | SHOW THE DISTANCE AS 39 FEET. |
| | 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. NOTE: CITY RECORDS SHOW |
| | THIS SYSTEM AS A 2 PSI SYSTEM. |
| | 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | 7) THE PLANS INDICATE AN EXISTING GAS METER AND CITY |
| | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. |
| | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE |
| | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE |
| | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. |
| | 8) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET |
| | OF THE 2-PSI METER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) SHOW THE PIPE SIZE TO THE THE EXISTING GAS LOAD. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 10) EXISTING PLANS ON FILE SHOW THE GAS SYSTEM AS A 2 |
| | PSI SYSTEM. SHOW THE LOCATION OF ALL EXISTING |
| | REGULATORS ON THE GAS PLAN.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 11) THE GAS DRAWING SHOWS TWO SHUTOFF VALVES IN THE GAS |
| | LINE TO THE GENERATOR. CLARIFY. |
| | 12) SINCE THIS IS AN EXISTING 2 PSI SYSTEM, A REGULATOR |
| | IS REQUIRED AT THE GENERATOR. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALATION INTRUCTIONS FOR THE |
| | REGULATOR. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED OR OUTDOOR INSTALLATION PER |
| | FFBC-FUEL GAS SEC.410.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |