Plan Review Notes
Plan Review Notes For Permit 20120587
Permit Number 20120587
Review Stop NFIP
Sequence Number 6
Notes
Date Text
2023-04-11 16:52:31IN ORDER TO BE APPROVED FOR PERMIT, THE
 PRE-CONSTRUCTION WILL NEED TO BE CORRECTED. THE FLOOD
 PROOFING CERTIFICATE CAN BE DEFERRED UNTIL THE FINAL
 INSPECTION.
  
 CORRECTIONS REQUIRED FOR PRE-CONSTRUCTION ELEVATION
 CERTIFICATE:
 A) SECTION A1. THE BUILDING OWNER IS RD IMV OWNER, LLC
 B) SECTION A2. THE BUILDING STREET ADDRESS IS 4328 N.
 FLAGLER DR.
 C) SECTION C2 A) MAKE A NOTE IN THE COMMENTS SECTION
 THAT THE BUILDING IS TO BE DRY FLOOD PROOFED UP TO THE
 DFE OF 9'-0" NAVD
  
 CORRECTIONS REQUIRED FOR THE FLOODPROOFING CERTIFICATE:
 A) THE DRAWING NUMBER 1 OF 2 IN THE PACKAGE WILL NEED
 TO BE REPLACE BY THE CORRECTED DRAWING 1'-6" WATER
 HEIGHT TO THE DFE OF 9.00" NAVD. THE CORRECTED DRAWING
 IS REQUIRED TO BE DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER PREPARING THE FLOODPROOFING CERTIFICATE.
  
 WHEN THE BUILDING IS COMPLETED IN ORDER TO RECIEVE THE
 C.O. SUBMIT A COMPLETED ELEVATION CERTIFICATE FOR THE
 FINISHED CONSTRUCTION ALONG WITH A FINAL BOUNDARY
 SURVEY WITH ELEVATIONS THAT MATCHES THE E.C. AND THE
 FLOODPROOFING CERTIFICATE.