| Plan Review Notes For Permit 20120587 |
| Permit Number |
20120587 |
|
| Review Stop |
NFIP |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2023-04-11 16:52:31 | IN ORDER TO BE APPROVED FOR PERMIT, THE | | | PRE-CONSTRUCTION WILL NEED TO BE CORRECTED. THE FLOOD | | | PROOFING CERTIFICATE CAN BE DEFERRED UNTIL THE FINAL | | | INSPECTION. | | | | | | CORRECTIONS REQUIRED FOR PRE-CONSTRUCTION ELEVATION | | | CERTIFICATE: | | | A) SECTION A1. THE BUILDING OWNER IS RD IMV OWNER, LLC | | | B) SECTION A2. THE BUILDING STREET ADDRESS IS 4328 N. | | | FLAGLER DR. | | | C) SECTION C2 A) MAKE A NOTE IN THE COMMENTS SECTION | | | THAT THE BUILDING IS TO BE DRY FLOOD PROOFED UP TO THE | | | DFE OF 9'-0" NAVD | | | | | | CORRECTIONS REQUIRED FOR THE FLOODPROOFING CERTIFICATE: | | | A) THE DRAWING NUMBER 1 OF 2 IN THE PACKAGE WILL NEED | | | TO BE REPLACE BY THE CORRECTED DRAWING 1'-6" WATER | | | HEIGHT TO THE DFE OF 9.00" NAVD. THE CORRECTED DRAWING | | | IS REQUIRED TO BE DIGITALLY SIGNED AND SEALED BY THE | | | ENGINEER PREPARING THE FLOODPROOFING CERTIFICATE. | | | | | | WHEN THE BUILDING IS COMPLETED IN ORDER TO RECIEVE THE | | | C.O. SUBMIT A COMPLETED ELEVATION CERTIFICATE FOR THE | | | FINISHED CONSTRUCTION ALONG WITH A FINAL BOUNDARY | | | SURVEY WITH ELEVATIONS THAT MATCHES THE E.C. AND THE | | | FLOODPROOFING CERTIFICATE. |
|