| 2022-08-22 07:48:03 | 4TH PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. DONE | | | | | | 2. DONE | | | | | | 3. THERE NEEDS TO BE ONE AT EACH HOT WATER SOURCE | | | INCLUDING THE WATER HEATER. THIS REQUIREMENT IS FOR ALL | | | HOT WATER, NOT JUST TEMPERED WATER AT PUBLIC HAND | | | WASHING STATIONS. 2020 FPC - 607.1.1 TEMPERATURE | | | LIMITING MEANS - THE THERMOSTAT CONTROL ON THE WATER | | | HEATER CANNOT BE THE LIMITING DEVICE FOR HOT WATER | | | DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE | | | FOR THE PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN | | | ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR | | | PUBLIC HANDWASHING 607.1.2/419.5. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|