Plan Review Notes
Plan Review Notes For Permit 20120587
Permit Number 20120587
Review Stop P
Sequence Number 4
Notes
Date Text
2022-08-22 07:48:034TH PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. THERE NEEDS TO BE ONE AT EACH HOT WATER SOURCE
 INCLUDING THE WATER HEATER. THIS REQUIREMENT IS FOR ALL
 HOT WATER, NOT JUST TEMPERED WATER AT PUBLIC HAND
 WASHING STATIONS. 2020 FPC - 607.1.1 TEMPERATURE
 LIMITING MEANS - THE THERMOSTAT CONTROL ON THE WATER
 HEATER CANNOT BE THE LIMITING DEVICE FOR HOT WATER
 DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE
 FOR THE PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN
 ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR
 PUBLIC HANDWASHING 607.1.2/419.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  