| 2023-02-21 14:57:42 | NOT RESULTED PENDING PEER REVIEW. |
| | |
| | ELEVATION CERTIFICATE REVIEW |
| | DENIED |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS. |
| | |
| | SECTION A1. THE OWNERS NAME IS SHOULD BE RD IMV OWNER |
| | LLC |
| | |
| | SECTION A2. THE ADDRESS SHOULD BE 4328 N. FLAGLER DR. |
| | |
| | SECTION A4. THIS SHOULD STATE NON-RESIDENTIAL. |
| | |
| | SECTION C2 E). SPECIFY THE LOWEST ELEVATION OF THE |
| | MACHINERY OR EQUIPMENT SERVICING THE BUILDING. |
| | |
| | SECTION C2 F). SPECIFY THE LOWEST ADJACENT GRADE NEXT |
| | TO THE BUILDING. (LAG) |
| | |
| | SECTION C2 G) SPECIFY THE HIGHEST ADJACENT GRADE NEXT |
| | TO THE BUILDING. (HAG) |
| | |
| | THE COMMENTS SECTION SHOULD SPECIFY THAT THE STRUCTURE |
| | IS BEING DRY FLOOD PROOFED UP TO THE DFE OF 9.0' NAVD |
| | 88. |
| | THE COMMENT (INCLUDING TYPE OF EQUIPMENT AND LOCATION, |
| | PER C2(E), IF APPLICABLE ) NEEDS TO BE CLEARIFIED. DO |
| | YOU MEAN THAT THE EQUIPMENT WILL BE LOCATED AT DFE OF |
| | 9.0' NAVD 88? |
| | |
| | DID NOT SEE THIS ON THE DRAWINGS FBC 1612.5 FLOOD |
| | HAZARD DOCUMENTATION. |
| | THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND |
| | SEALED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE BUILDING OFFICIAL: |
| | 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN |
| | COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES: |
| | 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS, |
| | CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT |
| | THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH |
| | ASCE 24. |
| | |
| | THE FLOOD PROOFING CERTIFICATE AND OTHER DOCUMENTS ARE |
| | REQUIRED TO BE AT 9.0' NAVD 88 IN ORDER TO MEET THE |
| | CITY OF WEST PALM BEACHES MORE STRINGENT REQUIREMENT OF |
| | A 2' FREEBOARD ABOVE BFE. |
| | |
| | |
| | |
| | |
| | |