Plan Review Notes
Plan Review Notes For Permit 20120587
Permit Number 20120587
Review Stop B
Sequence Number 4
Notes
Date Text
2022-12-22 11:15:49FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) WILL COMPLY. PROPERTY TO BE REPLATTED PRIOR TO
 ISSUANCE OF THE FIRST C.O. PER SECTION 6(2)(E)(II) OF
 RESOLUTION NO. 185-18 (THE "DEVELOPMENT ORDER").
  
 2) NOT RESOLVED. YOU HAVE INDICATED THAT YOU WISH TO
 DRY FLOOD PROOF THE BEACH CLUB, PLEASE SUBMIT THE
 FOLLOWING ITEMS. FBC 1612
  
 [CORRECTIONS REQUIRED TO PRECONSTRUCTION ELEVATION
 CERTIFICATE. SEE NFIP REVIEW.] A) A NEW
 PRE-CONSTRUCTION ELEVATION CERTIFICATE FOR THE DRY
 FLOOD PROOFING.
  
 COMPLIED. B) PROVIDE A DRY FLOOD PROOFING PLAN THAT
 INCLUDES WHERE THE PANELS ARE TO BE STORED AND WHO WILL
 BE RESPONSIBLE FOR INSTALLING THEM WHEN A FLOOD EVENT
 IS EXPECTED.
  
 [WATERPROOFING FOR THE WALLS IS NOT SHOWN OR SPECIFIED
 ON THE PLANS.] C) SHOW HOW THE WALLS WILL BE WATER
 PROOFED UP TO THE DESIGN FLOOD ELEVATION OF 9.0' NAVD
 88.
  
 [ ANY EQUIPMENT THAT CAN BE DAMAGED FROM FLOOD WATERS
 ARE REQUIRED TO BE PROTECTED.] D) THE PLANS SHOW
 KITCHEN EQUIPMENT AND A MEDIA CABINET IN THE OUTSIDE
 BAR AREA. SPECIFY HOW THAT AREA WILL BE PROTECTED FROM
 FLOOD WATERS.
  
 [ THERE IS NOTHING SHOWN ON THE PLANS OR ANY ENGINEER'S
 CALCULATIONS TO SHOW THAT THE WALLS ARE CAPABLE OF
 WITHSTANDING THE FORCES OF FLOOD WATERS. ] E) PROVIDE
 ENGINEERING TO SHOW THAT THE WALLS OF THE BEACH CLUB
 WILL BE ABLE TO WITHSTAND THE STATIC AND DYNAMIC
 PRESSURES FROM FLOOD WATERS UP TO THE DESIGN FLOOD
 ELEVATION OF 9.0' NAVD 88.
  
 I WILL SEND YOU THE REQUIRED FLOOD PROOFING CERTIFICATE
 FORM AND THE NFPI TECHNICAL BULLETIN ON THE
 REQUIREMENTS FOR DESIGN AND CERTIFICATION OF DRY FLOOD
 PROOFING... JUST LET ME KNOW WHERE TO SEND IT.
  
 (PREVIOUS COMMENT) SHEET A1.420 SPECIFIES THE FINISH
 FLOOR ELEVATION FOR THE BEACH CLUB AS 7.64' NAVD 88.
 SUBMIT THE PRE-CONSTRUCTION ELEVATION CERTIFICATE THAT
 WAS SUBMITTED FOR THE BEACH CLUB UNDER PERMIT #18100526
 HAS THE FFE AS 9.0' NAVD 88. PLEASE CLARIFY.
 THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A BASE
 FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 THE PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING HAS BEEN SUBMITTED. THE SECOND, A
 CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR
 FORMS AND THE THIRD A FINAL ELEV. CERT. BASED ON THE
 FINISHED BUILDING ARE TO BE SUBMITTED IN A TIMELY
 MANNER. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - FLOOD
 PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS FOR
 FLOOD HAZARD REDUCTION.
  
 3) WILL COMPLY. A SEPARATE ROOF PERMIT IS REQUIRED.
 PRIOR TO INSTALLATION, SUBMIT ROOF PERMIT APPLICATION
 WITH PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 AND ENGINEERING (IF APPLICABLE).
  
 4) WILL COMPLY. DEFERRED SUBMITTALS REQUESTED BY
 ARCHITECT. DOCUMENTS SHOWING COMPLIANCE ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL
 (ARCHITECT OR ENGINEER FOR PRODUCT APPROVALS AND OTHER
 SPECIFICATION DOCUMENTS, STRUCTURAL ENGINEER OF RECORD
 APPROVAL AND REVIEW IS REQUIRED FOR DELEGATED
 ENGINEERING). SUBMITTAL, REVIEW AND APPROVAL ARE
 REQUIRED PRIOR TO INSTALLATION.
  
 5) WILL COMPLY. COMPONENT & CLADDING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO
 THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN
 ON SHEET S6.0 - S6.3 PRIOR TO SUBMITTAL. IF PRODUCT
 APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED,
 ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM
 DESIGN PRESSURES.
  
 6) WILL COMPLY. SEPARATE PERMITS (APPLICATIONS, PLANS,
 AND FEES) ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) WILL COMPLY. CONSTRUCTION HOURS - 7AM TO 7PM
 MON-FRI, 8AM TO 8PM SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  