| 2022-05-28 10:04:25 | 3RD PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 1003.3.1 - THE GREASE INTERCEPTOR SHALL |
| | ONLY RECEIVE DISCHARGE FROM FIXTURES AND EQUIPMENT THAT |
| | ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. THE |
| | HANDSINKS AND ICEMAKER CANNOT DISCHARGE INTO THE GREASE |
| | WASTE. |
| | |
| | 2. CITY ORDINANCE SEC. 90 - 126 - THE POOL BACKWASH |
| | DISCHARGE CANNOT GO DIRECTLY INTO THE SANITARY UNLESS |
| | SPECIFICALLY AUTHORIZED BY THE CITY IN WRITING OR |
| | OTHERWISE TREATED 1ST. |
| | |
| | 3. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE |
| | THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE |
| | LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE |
| | A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT |
| | WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE |
| | REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING |
| | 607.1.2/419.5. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |