Plan Review Notes
Plan Review Notes For Permit 20120587
Permit Number 20120587
Review Stop NFIP
Sequence Number 3
Notes
Date Text
2022-12-22 12:46:12ELEVATION CERTIFICATE REVIEW
 DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS.
  
 SECTION A1. THE OWNERS NAME IS SHOULD BE RD IMV OWNER
 LLC
  
 SECTION A2. THE ADDRESS SHOULD BE 4328 N. FLAGLER DR.
  
 SECTION A4. SHOULD BE NON-RESIDENTIAL.
  
 SECTION C2(E). SHOULD SPECIFY THE LOWEST ELEVATION OF
 EQUIPMENT SERVICING THE BUILDING.
  
 THE DIGITAL SIGNATURE OF THE SURVEYOR COULD NOT BE
 VERIFIED.
  
 DID NOT SEE THIS ON THE DRAWINGS ??? FBC 1612.5 FLOOD
 HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
 SUBMIT THE FLOOD PROOFING CERTIFICATE FORM.
  
  
  