Plan Review Notes
Plan Review Notes For Permit 20120569
Permit Number 20120569
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-15 13:26:43PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: SERVICE EQUIPMENT SHALL BE MARKED WITH THE
 MAXIMUM AVAILBLE SHORT CIRCUT CURRENT AVAILABLE PER NEC
 110.24; E3606.4.
  
 1. PROVIDE NUMBER OF 3/0 CONDUCTORS BETWEEN THE METER
 AND NEW 200 AMP PANEL.
 NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1
  
 2. MAIN DISCONNECT (MDC) SHALL BE LOCATED AT POINT OF
 ENTRY OF SERVICE CONDUCTORS.
 E3601.6.2SERVICE DISCONNECT LOCATION.
 THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR INSIDE NEAREST THE POINT OF ENTRANCE OF THE
 SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL
 NOT BE INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE
 ACCESS TO THE DISCONNECT SERVING THE DWELLING UNIT IN
 WHICH THEY RESIDE. [230.70(A)(1), 230.72(C)]
  
 3. IDENTIFY LOCATION OF SERVICE AND C/U DISCONNECTS ON
 PLAN PAGE E-1. PROVIDE KEYED NOTES.
 SERVICE & METER
 FPL ELECTRIC SERVICE STANDARDS ? SECTION IV, A., 1.
 GENERAL. PG 1 OF 24
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. AFCI OUTLET NOTE # 2 ON PLAN PAGE E-3 SHOULD INCLUDE
 KITCHENS.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16
  
 5. HIGH EFFICACY LAMP NOTE # 5 ON PLAN PAGE E-3 SHOULD
 READ AS FOLLOWS:
 : "A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  