| 2020-12-15 13:26:43 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: SERVICE EQUIPMENT SHALL BE MARKED WITH THE |
| | MAXIMUM AVAILBLE SHORT CIRCUT CURRENT AVAILABLE PER NEC |
| | 110.24; E3606.4. |
| | |
| | 1. PROVIDE NUMBER OF 3/0 CONDUCTORS BETWEEN THE METER |
| | AND NEW 200 AMP PANEL. |
| | NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1 |
| | |
| | 2. MAIN DISCONNECT (MDC) SHALL BE LOCATED AT POINT OF |
| | ENTRY OF SERVICE CONDUCTORS. |
| | E3601.6.2SERVICE DISCONNECT LOCATION. |
| | THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A |
| | READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A |
| | BUILDING OR INSIDE NEAREST THE POINT OF ENTRANCE OF THE |
| | SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL |
| | NOT BE INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE |
| | ACCESS TO THE DISCONNECT SERVING THE DWELLING UNIT IN |
| | WHICH THEY RESIDE. [230.70(A)(1), 230.72(C)] |
| | |
| | 3. IDENTIFY LOCATION OF SERVICE AND C/U DISCONNECTS ON |
| | PLAN PAGE E-1. PROVIDE KEYED NOTES. |
| | SERVICE & METER |
| | FPL ELECTRIC SERVICE STANDARDS ? SECTION IV, A., 1. |
| | GENERAL. PG 1 OF 24 |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4. AFCI OUTLET NOTE # 2 ON PLAN PAGE E-3 SHOULD INCLUDE |
| | KITCHENS. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC |
| | 210.12; FBC RE E3902.16 |
| | |
| | 5. HIGH EFFICACY LAMP NOTE # 5 ON PLAN PAGE E-3 SHOULD |
| | READ AS FOLLOWS: |
| | : "A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1 |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |