| 2021-01-04 07:41:26 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20120560 |
| | 1/4/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | THE NEW PLANS AND RESUBMITTAL APPLICATION ARE FOR A |
| | DIFFERENT PROJECT AND ADDRESS- 242 CORTEZ RD. PLEASE |
| | RESPOND TO COMMENT #1 FROM THE 1ST REVIEW LISTED BELOW: |
| | PERMIT #20120560- 220 DYER RD. |
| | |
| | 1) THE COPIED PLAN SHEET P-103 REQUIRES AND AN ORIGINAL |
| | DIGITAL SEAL AND SIGNATURE OF THE ENGINEER OF RECORD- |
| | DAVID JONES PE IN COMPLIANCE WITH FL. STATUTE 471.025 |
| | AND SECTION 61G15.23.005 FAC. THE COPIED SHEET DID NOT |
| | TRANSMIT CLEARLY AND THE GAS RISER IS NOT LEGIBLE. |
| | PLEASE PROVIDE A CLEAN SIGNED AND SEALED PLAN SHEET FOR |
| | REVIEW- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |