2020-12-17 13:25:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION THAT THIS PROJECT IS
 REACTIVATION OF AN EXISTING SYSTEM. THIS OCCUPANY HAS
 BEEN VACANT FOR AN EXTENDED PERIOD OF TIME.
  
 THERE IS NO INDICATION IF THIS SYSTEM IS INSTALLED TO
 THE CURRENT EDITION OF NFPA 72, 2013.
  
 BASED ON THE ABOVE THIS SYTEM IS REQUIRED TO INSTALLED
 A A NEW FIRE LARM SYSTEM.
  
 PLEASE PROVIDE DETAILS AND ENSURE COMPLAINCE WITH THE
 CURRENT CODE.
  
  
 2) THERE ARE INDICATIONS OF SMOKE DETECTORS WITHIN THE
 CORRIDORS.
  
 IN A EFFORT TO REDUCE FALSE ALARMS, SMOKE DETECTION IN
 THE CORRIDORS IS NOT REQUIRED AND CAN BE REMOVED.
  
 PER NFPA 101 CH 30
  
 30.3.4.4 DETECTION. (RESERVED)
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A STATEMENT THAT
 THE OWNERS ARE REQUIREING THEM TO BE INSTALLED.
  
  
  
 3) THE PULL STATION BY THE WEST EXIT DOOR DOES NOT
 APPEAR TO BE WITHIN 5'.
  
 PER NFPA 72
  
 17.14.8.4 MANUAL FIRE ALARM BOXES SHALL BE LOCATED
 WITHIN 5 FT
 (1.5 M) OF EACH EXIT DOORWAY ON EACH FLOOR.
  
 PLEASE PROVIDE MEASURMENT ENSURING COMPLIANCE.
  
  
 3A) THERE IS NO INDICATION OF A PULL STATION ON THE 2ND
 FL BY THE STAIR.
  
 THIS STAIR IS ONE OF THE EXITS FROM THE 2ND FL
  
 PER NFPA 72
  
 17.14.8.4 MANUAL FIRE ALARM BOXES SHALL BE LOCATED
 WITHIN 5 FT
 (1.5 M) OF EACH EXIT DOORWAY ON EACH FLOOR.
  
 PLEASE PROVIDE A PULL STATION AT THIS STAIR.
  
  
 4) THERE ARE INDICATION OF HORN STROBES WITHIN THE
 LIVING UNITS; HOWEVER, COMPLIANCE WITH THE REQUIRED
 DECIBEL MAY BE COMPROMISED.
  
 PER NFPA 72
  
 18.4.5 SLEEPING AREA REQUIREMENTS.
 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO
 PROVIDE
 SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND
 LEVEL OF AT
 LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5
 DB
 ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT
 LEAST
 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA,
 WHICHEVER IS
 GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR
 RETRACTABLE
 PARTITION, IS LOCATED BETWEEN THE NOTIFICATION
 APPLIANCE AND
 THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED
 WITH THE
 BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW.
 18.4.5.3* EFFECTIVE JANUARY 1, 2014, AUDIBLE APPLIANCES
 PROVIDED
 FOR THE SLEEPING AREAS TO AWAKEN OCCUPANTS SHALL
 PRODUCE A LOW
 FREQUENCY ALARM SIGNAL THAT COMPLIES WITH THE
 FOLLOWING:
 (1) THE ALARM SIGNAL SHALL BE A SQUARE WAVE OR PROVIDE
 EQUIVALENT
 AWAKENING ABILITY.
 (2) THE WAVE SHALL HAVE A FUNDAMENTAL FREQUENCY OF 520
 HZ
 ? 10 PERCENT.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE MANUFACTURE
 SPECIFICATION SHEETS INDICATING THE PROPER TYPE. THE
 MINI HORN SPEC SHEET PROVIDED DOES NOT CLEARLY INDICTE
 COMPLIANCE.
  
  
 5) THERE ARE NO INDICATIONS THAT THIS SYTEM IS
 MONITORED.
  
 30.3.4.3.5 EMERGENCY FORCES NOTIFICATION SHALL BE
 ACCOMPLISHED IN
 ACCORDANCE WITH 9.6.4.
  
 9.6.4 EMERGENCY FORCES NOTIFICATION.
 9.6.4.1 WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 EMERGENCY FORCES NOTIFICATION SHALL BE PROVIDED TO
 ALERT THE
 MUNICIPAL FIRE DEPARTMENT AND FIRE BRIGADE (IF
 PROVIDED) OF FIRE OR
 OTHER EMERGENCY.
 9.6.4.2 WHERE EMERGENCY FORCES NOTIFICATION IS REQUIRED
 BY
 ANOTHER SECTION OF THIS CODE, THE FIRE ALARM SYSTEM
 SHALL BE
 ARRANGED TO TRANSMIT THE ALARM AUTOMATICALLY VIA ANY OF
 THE
 FOLLOWING MEANS ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION
 AND SHALL BE IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE
 ALARM
 AND SIGNALING CODE:
 (1) AUXILIARY FIRE ALARM SYSTEM
 (2) CENTRAL STATION FIRE ALARM SYSTEM
 (3) PROPRIETARY SUPERVISING STATION FIRE ALARM SYSTEM
 (4) REMOTE SUPERVISING STATION FIRE ALARM SYSTEM
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  