| 2022-09-19 14:48:36 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20120513 |
| | ADD: 1900 CONSULATE PL. SUITE: 705 |
| | CONT: MOSS DELCO INC. |
| | TEL: 561-644-0302 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. SEPT. 19TH/ 2022 |
| | ACTION: DENIED |
| | |
| | |
| | ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA |
| | STATUTE 553.80(2)(B) |
| | |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS??? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | |
| | |
| | 1) 3RD REQUEST. SAME NOTES FROM DESIGN PROFESSIONAL |
| | FROM 4/12/2021. THE PLAN REVIEW RESPONSE COMMENTS STATE |
| | THAT THE VALUE OF THE WORK HAS BEEN REVISED TO MORE |
| | ACCURATELY REFLECT THE WORK ACCOMPLISHED. THE VALUE OF |
| | WORK HAS NOT CHANGED NOR DECLARED. IT APPEARS WHEN |
| | READING THE PLAN REVIEW RESPONSES THAT THIS WORK HAS |
| | ALREADY BEEN COMPLETED. PLEASE RESPOND HAS THIS WORK |
| | BEEN COMPLETED WITHOUT A PERMIT. |
| | |
| | 1ST ROUND OF COMMENTS. THE DESCRIPTION OF WORK IS TO DO |
| | A REMODEL OF THE INTERIOR OF THE TENANT SPACE, KITCHEN |
| | CABINETS AND COUNTERTOP NEW SINK AND SUPPLY, 2 NEW |
| | VANITIES, TUB & SHOWER AND REPLACEMENT OF FLOORING WITH |
| | TILE WITH THE EXCEPTION OF THE FOYER, REMOVAL OF ALL |
| | DEBRIS AND COST OF DESIGN PROFESSIONAL AND THE |
| | CONTRACTOR OVERHEAD AND PROFIT. THE PERMIT VALUE |
| | DECLARED IS EXTREMELY LOW!!! |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION SECTION 109.3 BUILDING |
| | PERMIT VALUATION. IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2-4B) COMPLIED. |
| | |
| | 4C) BUILDING PROVISO: TO BE DETERMINED IN THE FIELD. |
| | 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS |
| | AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE |
| | FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT |
| | LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | |
| | 5) 3RD REQUEST. NO FLOORING INSULATION WAS SUBMITTED |
| | FOR THE 2ND OR 3RD REVIEW. THE RESPONSE STATES THE |
| | FLOOR SOUND INSULATION MATERIALS WERE INSTALLED AS PER |
| | THE BUILDING REQUIREMENTS FOR STANDARDS OF TILE FLOOR |
| | INSTALLATIONS. IF FIELD TESTING BY A CERTIFIED |
| | LABORATORY, PLEASE SUBMIT BOTH REQUIRED REPORTS FOR THE |
| | IIC AND STC REQUIREMENTS. COMMENT 5C THE FLAME SPREAD |
| | REPORT WILL ALSO NEED TO BE SATISFIED. |
| | |
| | 1ST ROUND COMMENT. THE PLANS STATED REPLACE ALL |
| | FLOORING, EXCEPT ENTRY, WITH NEW FLOOR TILE. FLOOR |
| | INSULATION (FBC-B 2017) OR TILE, STONE, MARBLE, VINYL |
| | AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 5A)3RD REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 5B) 3RD REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 5)3RD REQUEST. FLAME SPREAD- FBC-B 2020 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |