| 2021-03-08 09:39:51 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120513 |
| | 3/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE PLUMBING SCOPE OF WORK NOTES ON THE PLAN- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) PROVIDE SANITARY DRAINAGE AND WATER SUPPLY ISOMETRIC |
| | DRAWINGS FOR THE REMODELED KITCHEN AND MASTER BATH- |
| | SECTION 107.3.5.1.3 WPB. |
| | |
| | 3) PROVIDE THE WIDTH DIMENSION OF THE MASTER BATH |
| | TOILET SPACE, AND THE WIDTH OF THE SHOWER- SECTIONS |
| | 405.3.1 & 417.4 FBC P. |
| | |
| | 3) PROVIDE A MASTER BATH SHOWER PAN DETAIL- SECTION |
| | 421.5.2 FBC P. |
| | |
| | 4) PROVIDE PLUMBING NOTES FOR THE NEW SHOWER VALVE: |
| | 412.3 INDIVIDUAL SHOWER VALVES. INDIVIDUAL SHOWER AND |
| | TUB-SHOWER COMBINATION VALVES SHALL BE |
| | BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| | THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| | B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| | INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER |
| | COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE |
| | EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF |
| | THE VALVE TO 120 DEGREES F, WHICH SHALL BE FIELD |
| | ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| | UTILIZED FOR COMPLIANCE WITH THIS SECTION. |
| | |
| | 5) MP-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL FOR |
| | PIPES PENETRATING THE EXISTING SLAB- SECTIONS 315.1 FBC |
| | P, AND 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |