Plan Review Notes
Plan Review Notes For Permit 20120512
Permit Number 20120512
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-11 13:42:092ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20120512
 2/11/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW WERE NOT ADDRESSED AND THE
 REQUESTED RESPONSE NARRATIVE WAS NOT PROVIDED. PLEASE
 ADDRESS THE COMMENTS.
  
 1) PROVIDE A SITE PLAN AND A PLUMBING PLAN SHOWING THE
 WATER SERVICE AND SANITARY DRAINAGE SYSTEMS FOR THE
 PROPOSED TRAILER. PROVIDE DETAILS INCLUDING:
  
 A) POTABLE WATER SERVICE PIPE RUN FROM POINT OF
 CONNECTION AT THE CITY MAIN TO THE TEMPORARY TRAILER-
 SECTIONS 602.1 & 602.2 FBC P.
  
 B) TYPE, SIZE AND BURIAL DEPTH OF WATER SERVICE PIPE-
 SECTIONS 602.1, 602.2, 603.1 AND TABLE 605.3 FBC P.
  
 C) BACKFLOW PREVENTER LOCATION AND TYPE TO BE
 INSTALLED. PLEASE NOTE THAT THE BACKFLOW PREVENTER
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT- 608.1 FBC
 P.
  
 D) LOCATION AND TYPE OF MAIN SHUTOFF VALVE- 606.1 FBC
 P.
  
 E) SANITARY SEWER LINE RUN FROM THE TRAILER TO THE
 POINT OF CONNECTION TO THE CITY SEWER LINE- 701.3 FBC
 P.
  
 F) TYPE, SIZE, BURIAL DEPTH OF THE SANITARY SEWER PIPE
 AND LOCATIONS OF CLEANOUTS- TABLE 702.3. AND SECTIONS
 708.1.2 & 708.1.3 FBC P.
  
 2) PLEASE NOTE IF HOLDING TANKS ARE TO BE INSTALLED FOR
 SANITY SEWER IN LIEU OF CONNECTING TO THE CITY SEWER,
 PLEASE SHOW THEIR LOCATIONS AND SIZES ON THE PLAN AND
 ALL PIPING RUNS. SUBMIT A COPY OF THE CONTRACT FOR THE
 TANKS THAT INCLUDES THE PUMP-OUT SCHEDULE- SECTION
 108.1 WPB.
  
 3) BACKFLOW PREVENTER: A FLORIDA LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE WPB BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  