| Date |
Text |
| 2021-02-11 13:42:09 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120512 |
| | 2/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST |
| | REVIEW LISTED BELOW WERE NOT ADDRESSED AND THE |
| | REQUESTED RESPONSE NARRATIVE WAS NOT PROVIDED. PLEASE |
| | ADDRESS THE COMMENTS. |
| | |
| | 1) PROVIDE A SITE PLAN AND A PLUMBING PLAN SHOWING THE |
| | WATER SERVICE AND SANITARY DRAINAGE SYSTEMS FOR THE |
| | PROPOSED TRAILER. PROVIDE DETAILS INCLUDING: |
| | |
| | A) POTABLE WATER SERVICE PIPE RUN FROM POINT OF |
| | CONNECTION AT THE CITY MAIN TO THE TEMPORARY TRAILER- |
| | SECTIONS 602.1 & 602.2 FBC P. |
| | |
| | B) TYPE, SIZE AND BURIAL DEPTH OF WATER SERVICE PIPE- |
| | SECTIONS 602.1, 602.2, 603.1 AND TABLE 605.3 FBC P. |
| | |
| | C) BACKFLOW PREVENTER LOCATION AND TYPE TO BE |
| | INSTALLED. PLEASE NOTE THAT THE BACKFLOW PREVENTER |
| | SHALL BE INSTALLED UNDER A SEPARATE PERMIT- 608.1 FBC |
| | P. |
| | |
| | D) LOCATION AND TYPE OF MAIN SHUTOFF VALVE- 606.1 FBC |
| | P. |
| | |
| | E) SANITARY SEWER LINE RUN FROM THE TRAILER TO THE |
| | POINT OF CONNECTION TO THE CITY SEWER LINE- 701.3 FBC |
| | P. |
| | |
| | F) TYPE, SIZE, BURIAL DEPTH OF THE SANITARY SEWER PIPE |
| | AND LOCATIONS OF CLEANOUTS- TABLE 702.3. AND SECTIONS |
| | 708.1.2 & 708.1.3 FBC P. |
| | |
| | 2) PLEASE NOTE IF HOLDING TANKS ARE TO BE INSTALLED FOR |
| | SANITY SEWER IN LIEU OF CONNECTING TO THE CITY SEWER, |
| | PLEASE SHOW THEIR LOCATIONS AND SIZES ON THE PLAN AND |
| | ALL PIPING RUNS. SUBMIT A COPY OF THE CONTRACT FOR THE |
| | TANKS THAT INCLUDES THE PUMP-OUT SCHEDULE- SECTION |
| | 108.1 WPB. |
| | |
| | 3) BACKFLOW PREVENTER: A FLORIDA LICENSED PLUMBING |
| | CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND |
| | SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE WPB BUILDING |
| | DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL |
| | OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |