Plan Review Notes
Plan Review Notes For Permit 20120481
Permit Number 20120481
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-22 16:16:232NDREVIEW FBC-2017 PLUMBING
 PERMIT- 20120481
 2/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NOTES HAVE BEEN ADDED IN CAP LETTERS. PLEASE COMPLY.
  
 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE
 DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD
 IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND
 FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC. 2ND
 REQUEST FOR MARKED UP SHEET G-1.1 BY CLAREN
 ARCHITECTURE TO BE DIGITALLY SIGNED AND SEALED.
  
 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW
 PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. A RED
 LINE NOTE WILL BE ADDED TO THE APPROVED SIGNED AND
 SEALED PLAN.
  
 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND
 REQUIRED SHUTOFF VALVES AT THE METER AND AT THE
 TRAILER- SECTION 606.1 FBC P. SHUTOFF VALVES NOT SHOWN.
 A RED LINE NOTE WILL BE ADDED TO THE APPROVED PLAN.
  
 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS. A RED
 LINE NOTE FOR CLEANOUTS WILL BE ADDED TO THE APPROVED
 PLAN.
  
 NEW COMMENT
 1) THE COMMENT RESPONSE NARRATIVE STATES THE 1 IN. PVC
 WATER SERVICE LINE WILL BE RUN ABOVEGROUND. PLEASE
 INDICATE HOW THE SERVICE LINE WILL BE SECURED AND
 PROTECTED FROM DAMAGE- SECTION 305.7 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-02-22 16:13:472NDREVIEW FBC-2017 PLUMBING
 PERMIT- 20120481
 2/22/2021CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NOTES HAVE BEEN ADDED IN CAP LETTERS. PLEASE COMPLY.
 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE
 DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD
 IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND
 FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC. 2ND
 REQUEST FOR MARKED UP SHEET G-1.1 BY CLAREN
 ARCHITECTURE TO BE DIGITALLY SIGNED AND SEALED.
 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW
 PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. A
 SEPARTATE PERMIT IS REQUIRED FOR THE BACKFLOW. A RED
 LINE NOTE WILL BE ADDED TO THE APPROVED PLAN.
 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND
 REQUIRED SHUTOFF VALVES AT THE METER AND AT THE
 TRAILER- SECTION 606.1 FBC P. SHUTOFF VALVES NOT SHOWN.
 A RED LINE NOTE WILL BE ADDED TO APPROVED PLAN.
 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS. A RED
 LINE NOTE FOR CLEANOUTS WILL BE ADDED TO APPROVED
 DRAWING.
 NEW COMMENT
 1) THE COMMENT RESPONSE NARRATIVE STATES THE 1 IN. PVC
 WATER SERVICE LINE WILL BE RUN ABOVEGROUND. PLEASE
 INDICATE HOW THE SERVICE LINE WILL BE SECURED AND
 PROTECTED FROM DAMAGE- SECTION 305.7 FBC P.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  