| 2020-12-23 12:05:51 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120481 |
| | 12/23/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE |
| | DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD |
| | IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND |
| | FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC. |
| | |
| | 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW |
| | PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND |
| | REQUIRED SHUTOFF VALVES AT THE METER AND AT THE |
| | TRAILER- SECTION 606.1 FBC P. |
| | |
| | 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER |
| | DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS. |
| | |
| | 5) THE $2800.00 PERMIT VALUE APPEARS LOW FOR THE ENTIRE |
| | SCOPE OF THE PROJECT. PLEASE PROVIDE COPIES OF SIGNED |
| | CONTRACTS AND/OR ESTIMATES AND INVOICES FOR THE |
| | BUILDING, PLUMBING AND ELECTRICAL SITE WORK, TRAILER |
| | AND HOLDING TANK INSTALLATIONS, TRAILER LEASING AND |
| | HOLDING TANK MAINTENANCE AGREEMENTS. PLEASE INCLUDE A |
| | PUMP-OUT SCHEDULE FOR THE TANK. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |