| Notes |
| Date |
Text |
| 2020-12-31 12:47:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT APPEARS TO RESTRICT THE ONLY | | | EGRESS ROUTE FROM THE UNITS. | | | | | | PER NFPA 101, CH 4 | | | | | | 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT | | | OPERATIONS. | | | 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE | | | PERMITTED TO | | | BE OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, | | | OR ADDITIONS | | | ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE | | | PROTECTION | | | FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR | | | THE PORTION | | | OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES | | | ACCEPTABLE TO | | | THE AUTHORITY HAVING JURISDICTION ARE IN PLACE. | | | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK THAT INCLUDES | | | HOW THE EGRESS WILL BE MAINTAINED DURING THE ENTIRE | | | DEMO AND INSTALLATION PROCESS. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|