| 2021-01-06 13:51:54 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120440 |
| | 1/6/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P0.0.0: PLEASE PROVIDE PIPE MATERIAL SPECIFICATIONS |
| | FOR SANITARY DRAINS AND VENTS, WATER DISTRIBUTION AND |
| | SUPPLY LINES, CONDENSATE DISPOSAL- SECTION 303.2 FBC P. |
| | BASED ON MECHANICAL PLAN NOTES IT APPEARS PIPING MAY BE |
| | RUNNING THROUGH PLENUM RATED SPACES. |
| | |
| | 2) P0.0.0: IT APPEARS A PUMP WILL BE REQUIRED FOR THE |
| | NEW CONDENSATE PIPING. PLEASE SHOW THE LOCATION AND |
| | PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECTION |
| | 314.2.1 FBC P. PLEASE NOTE CONDENSATE DRAINS SHALL BE |
| | TRAPPED AS REQUIRED BY THE EQUIPMENT OR APPLIANCE |
| | MANUFACTURER- 314.2.4. |
| | |
| | 3) P0.0.0 & P1.1.2: PLEASE INCLUDE THE BACKFLOW |
| | PREVENTERS IN THE FIXTURE SCHEDULE- TABLE 608.1 FBC P. |
| | |
| | 4) A1.1.1 & A3.0.1: SHOW THE CLEAR FLOOR SPACE DIAGRAM |
| | AND DIMENSIONS FOR THE NEW KITCHEN SINK- SECTION 606.2 |
| | FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |