| Plan Review Notes For Permit 20120440 |
| Permit Number |
20120440 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-07 10:53:57 | INTERIOR OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWINGS SHOW CORRIDOR WALLS BETWEEN ELEVATOR AND | | | OFFICES AS NON FIRE RATED. PLEASE SHOW HOW THE EXISTING | | | ELEVATOR HOISTWAY IS PROTECTED PER FBC 3006.3 | | | 2) PLEASE SHOW THE REQUIRED MANEUVERING CLEARANCE AT | | | DOOR (1403) FROM INSIDE THE CONFERENCE ROOM TO COMPLY | | | WITH FBC ACCESSIBILITY 404.2.4 | | | 3) PLEASE SHOW THE REQUIRED FLOOR SPACE FOR ALL | | | ACCESSIBLE ELEMENTS SUCH AS SINK, MICROWAVE, | | | REFRIGERATOR ETC. PER FBC 305 |
|