| Plan Review Notes For Permit 20120429 |
| Permit Number |
20120429 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-11 12:55:52 | STAIR SHOP DRAWINGS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW STAIR RISER HEIGHT AND TREAD DEPTH TO | | | COMPLY WITH FBC 1011.5.2 RISER HEIGHT AND TREAD DEPTH. | | | STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM | | | AND 4 INCHES (102 MM) MINIMUM. THE RISER HEIGHT SHALL | | | BE MEASURED VERTICALLY BETWEEN THE NOSINGS OF ADJACENT | | | TREADS. RECTANGULAR TREAD DEPTHS SHALL BE 11 INCHES | | | (279 MM) MINIMUM MEASURED HORIZONTALLY BETWEEN THE | | | VERTICAL PLANES OF THE FOREMOST PROJECTION OF ADJACENT | | | TREADS AND AT A RIGHT ANGLE TO THE TREAD?S NOSING. | | | 2) SHOP DRAWINGS SHOULD BE REVIEWED AND MARKED APPROVED | | | BY THE BUILDING DESIGNER OF RECORD FBC WPB 107.3.4.1 | | | 3) PLEASE SHOW THE STAIR RISERS TO COMPLY WITH FBC | | | 1011.5.5.3 (1).SOLID RISERS ARE NOT REQUIRED FOR | | | STAIRWAYS THAT ARE NOT REQUIRED TO COMPLY WITH SECTION | | | 1009, PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT | | | PERMIT THE PASSAGE OF A SPHERE WITH A DIAMETER OF 4 | | | INCHES (102 MM). (DRAWINGS SHOW = 4" WHICH WILL NOT | | | REJECT A 4" OBJECT). |
|