| 2021-01-28 15:19:03 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120427 |
| | 1/28/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- F |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED: |
| | |
| | 1) SHEETS A1.1.1 & A.3.01: PLEASE SHOW THE CLEAR FLOOR |
| | SPACE PARALLEL APPROACH DIAGRAM AND DIMENSIONS FOR THE |
| | NEW LOUNGE SINK, DISHWASHER AND ICE MACHINE- SECTIONS |
| | 305.1 & 804.6, & 804.6.3 FBC ACC. DETAIL 2/3.02: SINK |
| | HEIGHT NOT SHOWN- SECTION 606.3. |
| | |
| | 2) SHEETS P1.02 & P2.00: PLANS SHOW CONDENSATION FROM |
| | THE ICE MAKER DRAINING INTO THE SANITARY SYSTEM WHICH |
| | IS PROHIBITED- SEC. 90-126 WPB CODE OF ORDINANCES. THE |
| | DRAINAGE SHALL BE DISCHARGED TO AN APPROVED PLACE OF |
| | DISPOSAL SUCH AS THE STORM DRAINAGE SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |