2021-01-29 16:59:36BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20120427
  
 1- SHEET ALS1.1:
 A)THE TERRACE SHOWN ON THE LEFT HAND SIDE IS PART OF
 THE SUITE 1030. OCCUPANT LOAD CALCULATIONS NEED TO BE
 REVISED. NEED TO ADD THE OCCUPANT LOAD OF THE TERRACE.
 NOTE: TERRACE OCCUPANT LOAD IS BASED ON ASSEMBLY USE
 NOT BUSINESS. SEE TABLE 1004.1.2 FBC-BUILDING.
  
 B)BASED ON THE ADDITIONAL OCCUPANT LOAD OF THE TERRACE,
 IT LOOKS LIKE THE ROOM IDENTIFIED AS "POINT 72/SUITE
 1030 AT THE BOTTOM OF THE FLOOR PLAN NEEDS TO HAVE TWO
 "EXIT ACCESS DOORWAYS". ONLY ONE WAS PROVIDED. REVISE
 AS REQUIRED. SEC. 1006.2.1 FBC-BUILDING.
  
 C)THE EGRESS TRAVEL DISTANCE FROM THE TERRACE AREA TO
 THE EXIT NEEDS TO BE SHOWN ON THE FLOOR PLAN AND REVISE
 THE TRAVEL DISTANCE UNDER CODE DATA. SEC. 1017.3
 FBC-BUILDING.
  
 D)CLARIFY OCCUPANT CALCULATIONS. WHY THE MULTI-TENANT
 CORRIDOR HAS AN OCCUPANT LOAD OF 21 OCCUPANTS?. ISN'T
 THIS CORRIDOR TO BE USED FOR ALL TENANTS IN THIS
 FLOOR?. WHY USING 100 S.F. PER OCCUPANT?. THERE ARE
 OTHER OCCUPANCIES IN THIS FLOOR BESIDES BUSINESS. FOR
 EXAMPLE FLOOR PLAN SHOWS A FITNESS AREA AND CONFERENCE
 AREA.
 PROVIDE CALCULATIONS FOR SIZING THE CORRIDOR WIDTH AND
 CAPACITY BASED ON THE OVERALL OCCUPANCY OF ENTIRE FLOOR
 AS REQUIRED BY SEC. 1020.2 FBC-BUILDING.
 NOTE: COORDINATE WITH ITEM #3(B) BELOW.
  
 E)MISSING EXIT SIGN ON BOTH SIDES OF WALL DIVIDING THE
 SUITE 1030 AND THE "EXPANSION". (THIS SIGN ALLOWS
 OCCUPANTS TO KNOW THAT THERE IS ANOTHER EXIT ACCESS
 DOOR ON THAT DIRECTION). SEE CLOUDED AREA WITH DELTA
 #2. SEC. 1013.1 FBC-BUILDING.
  
 F)REQUIRED NUMBER OF EXITS SHOWN UNDER CODE DATA IS
 INCORRECT. TWO TWO EXIT ACCESS DOORWAYS ARE REQUIRED
 FROM SUITE 1030. SEC. 1006.2.1 FBC-BUILDING.
  
 2- THIS PERMIT APPLICATION IS FOR THE MULTI-TENANT
 CORRIDOR ALSO. THERE SOME DOORS THAT SWING OUT INTO THE
 CORRIDOR. IT LOOKS LIKE THIS DOORS WILL BLOCK THE
 CORRIDOR MEANS OF EGRESS. NOTE: THIS COMMENT APPLIES TO
 THE MECHANICAL ROOM, CONFERENCE AREA AND STORAGE ROOM.
 REVISE AS REQUIRED ALL PLANS SHOWING THESE DOORS. SEC.
 1005.7.1 FBC-BUILDING.
  
 3- SHEET A1.1.5:
 A)THERE IS A 4'-10" DIMENSION FOR RECESSED DOOR #900E
 AT THE BOTTOM RIGHT OF PLAN. SHOW HOW COMPLYING WITH
 THE 18 INCHES MANEUVERING CLEARANCE REQUIRED BY SEC.
 404.2.4 FBC-ACCESSIBILITY.
  
 B)PROVIDE CALCULATIONS FOR SIZING THE CORRIDOR WIDTH
 AND CAPACITY BASED ON THE OVERALL OCCUPANCY OF ENTIRE
 FLOOR AS REQUIRED BY SEC. 1020.2 FBC-BUILDING.
 NOTE: COORDINATE WITH ITEM #1(D) ABOVE.
  
 4- PROVISO:
 A)SOLAR SHADES TO COMPLY WITH THE TESTS REQUIRED BY
 SECTION 806.4 FBC-BUILDING FOR COMBUSTIBLE DECORATIVE
 MATERIALS EXCEPTION #3 OF SECTION 806.3 FBC-BUILDING
 B)INTERIOR FLOOR-WALL RUBBER BASE BASE TO COMPLY WITH
 TEST REQUIRED BY SECTION 806.8 FBC-BUILDING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER