| 2021-01-29 16:59:36 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | PERMIT #20120427 |
| | |
| | 1- SHEET ALS1.1: |
| | A)THE TERRACE SHOWN ON THE LEFT HAND SIDE IS PART OF |
| | THE SUITE 1030. OCCUPANT LOAD CALCULATIONS NEED TO BE |
| | REVISED. NEED TO ADD THE OCCUPANT LOAD OF THE TERRACE. |
| | NOTE: TERRACE OCCUPANT LOAD IS BASED ON ASSEMBLY USE |
| | NOT BUSINESS. SEE TABLE 1004.1.2 FBC-BUILDING. |
| | |
| | B)BASED ON THE ADDITIONAL OCCUPANT LOAD OF THE TERRACE, |
| | IT LOOKS LIKE THE ROOM IDENTIFIED AS "POINT 72/SUITE |
| | 1030 AT THE BOTTOM OF THE FLOOR PLAN NEEDS TO HAVE TWO |
| | "EXIT ACCESS DOORWAYS". ONLY ONE WAS PROVIDED. REVISE |
| | AS REQUIRED. SEC. 1006.2.1 FBC-BUILDING. |
| | |
| | C)THE EGRESS TRAVEL DISTANCE FROM THE TERRACE AREA TO |
| | THE EXIT NEEDS TO BE SHOWN ON THE FLOOR PLAN AND REVISE |
| | THE TRAVEL DISTANCE UNDER CODE DATA. SEC. 1017.3 |
| | FBC-BUILDING. |
| | |
| | D)CLARIFY OCCUPANT CALCULATIONS. WHY THE MULTI-TENANT |
| | CORRIDOR HAS AN OCCUPANT LOAD OF 21 OCCUPANTS?. ISN'T |
| | THIS CORRIDOR TO BE USED FOR ALL TENANTS IN THIS |
| | FLOOR?. WHY USING 100 S.F. PER OCCUPANT?. THERE ARE |
| | OTHER OCCUPANCIES IN THIS FLOOR BESIDES BUSINESS. FOR |
| | EXAMPLE FLOOR PLAN SHOWS A FITNESS AREA AND CONFERENCE |
| | AREA. |
| | PROVIDE CALCULATIONS FOR SIZING THE CORRIDOR WIDTH AND |
| | CAPACITY BASED ON THE OVERALL OCCUPANCY OF ENTIRE FLOOR |
| | AS REQUIRED BY SEC. 1020.2 FBC-BUILDING. |
| | NOTE: COORDINATE WITH ITEM #3(B) BELOW. |
| | |
| | E)MISSING EXIT SIGN ON BOTH SIDES OF WALL DIVIDING THE |
| | SUITE 1030 AND THE "EXPANSION". (THIS SIGN ALLOWS |
| | OCCUPANTS TO KNOW THAT THERE IS ANOTHER EXIT ACCESS |
| | DOOR ON THAT DIRECTION). SEE CLOUDED AREA WITH DELTA |
| | #2. SEC. 1013.1 FBC-BUILDING. |
| | |
| | F)REQUIRED NUMBER OF EXITS SHOWN UNDER CODE DATA IS |
| | INCORRECT. TWO TWO EXIT ACCESS DOORWAYS ARE REQUIRED |
| | FROM SUITE 1030. SEC. 1006.2.1 FBC-BUILDING. |
| | |
| | 2- THIS PERMIT APPLICATION IS FOR THE MULTI-TENANT |
| | CORRIDOR ALSO. THERE SOME DOORS THAT SWING OUT INTO THE |
| | CORRIDOR. IT LOOKS LIKE THIS DOORS WILL BLOCK THE |
| | CORRIDOR MEANS OF EGRESS. NOTE: THIS COMMENT APPLIES TO |
| | THE MECHANICAL ROOM, CONFERENCE AREA AND STORAGE ROOM. |
| | REVISE AS REQUIRED ALL PLANS SHOWING THESE DOORS. SEC. |
| | 1005.7.1 FBC-BUILDING. |
| | |
| | 3- SHEET A1.1.5: |
| | A)THERE IS A 4'-10" DIMENSION FOR RECESSED DOOR #900E |
| | AT THE BOTTOM RIGHT OF PLAN. SHOW HOW COMPLYING WITH |
| | THE 18 INCHES MANEUVERING CLEARANCE REQUIRED BY SEC. |
| | 404.2.4 FBC-ACCESSIBILITY. |
| | |
| | B)PROVIDE CALCULATIONS FOR SIZING THE CORRIDOR WIDTH |
| | AND CAPACITY BASED ON THE OVERALL OCCUPANCY OF ENTIRE |
| | FLOOR AS REQUIRED BY SEC. 1020.2 FBC-BUILDING. |
| | NOTE: COORDINATE WITH ITEM #1(D) ABOVE. |
| | |
| | 4- PROVISO: |
| | A)SOLAR SHADES TO COMPLY WITH THE TESTS REQUIRED BY |
| | SECTION 806.4 FBC-BUILDING FOR COMBUSTIBLE DECORATIVE |
| | MATERIALS EXCEPTION #3 OF SECTION 806.3 FBC-BUILDING |
| | B)INTERIOR FLOOR-WALL RUBBER BASE BASE TO COMPLY WITH |
| | TEST REQUIRED BY SECTION 806.8 FBC-BUILDING. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |