| 2021-01-22 10:55:10 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120426 |
| | 1/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A3.01 & P4.01: SHOW THE WATER SUPPLY AND |
| | SANITARY DRAIN AND VENT PIPING FOR THE DISHWASHER AND |
| | ICE MACHINE IN THE ISOMETRIC DRAWINGS- SECTIONS 409.2, |
| | 604.3, 604.4, 604.4, 802.1 FBC P. PLEASE INCLUDE THE |
| | LOCATIONS FOR THE REQUIRED WATER HAMMER ARRESTORS AND |
| | BACKFLOW PREVENTERS- SECTIONS 604.9 AND 608.3. PLEASE |
| | NOTE THAT CONDENSATION FROM COOLING COILS SHALL NOT |
| | DRAIN IN THE SANITARY SYSTEM- SEC. 90-126 WPB CODE OF |
| | ORDINANCES. |
| | |
| | 2) SHEETS A.3.01 & A.4.03: PLEASE SHOW THE CLEAR FLOOR |
| | SPACE PARALLEL APPROACH DIAGRAM AND DIMENSIONS FOR THE |
| | NEW LOUNGE SINK, DISHWASHER AND ICE MACHINE- SECTIONS |
| | 305.1 & 804.6, & 804.6.3 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |