| Plan Review Notes For Permit 20120426 |
| Permit Number |
20120426 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-26 10:26:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E9.01 | | | | | | PANEL SCHEDULES NEED TO ADD SUITE NUMER TO THE PANEL | | | SCHEDULE FOR BRK BRANCH CIRCUIT NUMBERS 408.4 | | | | | | PAGE E4.02 | | | | | | RISER SHOULD INCLUDE WIRE SIZES ON FEEDERS TO AND FROM | | | TRANSFORMER. 215.5 |
|