Plan Review Notes
Plan Review Notes For Permit 20120426
Permit Number 20120426
Review Stop E
Sequence Number 1
Notes
Date Text
2021-01-26 10:26:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E9.01
  
 PANEL SCHEDULES NEED TO ADD SUITE NUMER TO THE PANEL
 SCHEDULE FOR BRK BRANCH CIRCUIT NUMBERS 408.4
  
 PAGE E4.02
  
 RISER SHOULD INCLUDE WIRE SIZES ON FEEDERS TO AND FROM
 TRANSFORMER. 215.5