| Plan Review Notes For Permit 20120408 |
| Permit Number |
20120408 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-07 08:36:47 | PLEASE PROVIDE MATERIALS OF FENCE | | | | | | PLEASE PROVIDE SCREENING MATERIALS. WIND SCREENING | | | SHALL BE SUBSTANTIAL ENOUGH TO AVOID RIPS OR TEARS AND | | | SHALL NO LESS THAN 85 PERCENT OPACITY. | | | NO SCREENING GRAPHICS SHALL BE PERMITTED FOR THIS FENCE | | | FOR STAGING/CONSTRUCTION TRAILER ASSOCIATED WITH THE | | | DEVELOPMENT AND/OR CONSTRUCTION GROUP | | | | | | NO FENCE CAN BE WITHIN THE CITY ROW WITHOUT A ROW | | | PERMIT - PLEASE ADJUST FENCE LOCATION ILLUSTRATION IF | | | NOT WITHIN ROW | | | | | | IS THERE ALSO A GATE AT THE REAR (ALLEY SIDE) OF THE | | | FENCE OR WILL ALL EQUIPIMENT AND MATERIAL BE | | | TRANSPORTED ON 2ND STREET? | | | | | | ADDED FIRE STOP FOR INGRESS/EGRESS REVIEW | | | | | | 4X PERMIT FEE ADDED FOR INSTLLATION WITHOUT PERMIT | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | 561 822 1426 | | | [email protected] |
|