Plan Review Notes
Plan Review Notes For Permit 20120399
Permit Number 20120399
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-09 15:13:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE ADDRESS ON THE APPLICATION INDICATES 901 S
 FLAGLER AND THE SUBMITTED PLAN SHEETS INDICATE 1101 S
 OLIVE AVE.
  
 PLEASE CORRECT TO THE PROPER ADDRESS.
  
  
  
 2) THERE ARE NO INDICATIONS OF EXISTING FIRE SPRINKLER
 PROTECTION.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM, INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND A NOTE OF
 ACKNOWLEDGEMENT
  
  
  
 3) THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES/EQUIPMENT.
  
 ANY WORK ON THE FIRE ALARM SYSTEM, INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND A NOTE OF
 ACKNOWLEDGEMENT
  
  
 4) THERE IS NO INDICATION OF COMPLAINCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE REVIEW, ENSURE COMPLAINCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  