Plan Review Notes
Plan Review Notes For Permit 20120390
Permit Number 20120390
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-29 15:38:0412/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET SP01, PLEASE PROVIDE CODE YEAR AND
 PLUMBING REFERENCED USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 101.4 REFERENCED CODES.
  
 2. A SET OF PLANS HAS BEEN SUBMITTED THAT ARE NOT CLEAR
 AND BURRY. PLEASE SUBMIT OR PROVIDE A CLEAR SET OF
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1.4
 QUALITY OF BUILDING PLANS.
  
 3. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 4. ON SHEET P01;
  
 A. THE WATER RISER ISOMETRIC DIAGRAM SHOWS UNITS
 UPSTAIRS AND DOWNSTAIRS TIED TOGETHER. THESE ARE CALLED
 OUT AS SEPARATE UNITS AND NEED TO BE ONE VALVE ON THE
 FIRST FLOOR AND ANOTHER ON THE SECOND FLOOR. EACH
 DWELLING UNIT SHALL BE PROVIDED WITH AN ACCESSIBLE MAIN
 SHUTOFF VALVE NEAR THE WATER SERVICE ENTRANCE PER THE
 2017 FBC SEC. R 2903.9.1 SERVICE VALVE.
  
 B. PLEASE SHOW THE WATER HAMMERS ON THE DISHWASHER,
 REFRIGERATOR, AND WASHING MACHINE ON THE ISOMETRIC
 DRAWING PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC. R
 2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 D. HOT WATER PIPES IN THE FIRST FLOOR NOT IN CONDITION
 SPACE NEED SHALL BE INSULATED WITH A MINIMUM R-3 PER
 THE 2017 FBC SEC. RE 403.5.3.
  
 E. IF REQUIRED, PLEASE PROVIDE DETAIL FOR THE WATER
 HEATER AND HOW IT WILL DRAIN OUTSIDE WITH THE METHOD
 USED TO PREVENT THE RODENT FROM ENTERING THROUGH THAT
 DRAIN PER THE 2017 FBC R 2801.6.2 AND 2017 FBC R
 2606.1.
  
 F. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER AND LOCATION TO ACCESS IT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. PLEASE REMOVE ANY DETAILS THAT DO NOT PERTAIN TO
 THIS STRUCTURE, I. E. (FLOOR DRAIN) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET P-2 FOR THE SANITARY ISOMETRIC;
  
 A. PLEASE SEPARATE EACH FLOOR TO ITS SEPARATE SYSTEM TO
 EACH DWELLING AS THERE ARE CALLED OUT TWO DIFFERENT
 UNITS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE KITCHEN SINK MUST BE DOWNSTREAM OF THE WET VENT
 BATHROOM GROUP. THE KITCHEN SINK CANNOT DISCHARGE INTO
 THE WET VET OF A BATHROOM GROUP. IT MUST BE DOWNSTREAM
 PER THE 2017 FBC SECTION R3108.1 HORIZONTAL WET VENT
 PERMITTED.
  
 C. THE SHOWER DOWNSTAIRS HAS A DRY VENT AND REQUIRES A
 WET VENT PER THE 2017 FBC SEC. P3108.2.1.
  
 D. THE UPSTAIRS SHOWER HAS TO BE RE-VENTED SIX INCHES
 ABOVE THE FLOOD RIM LEVEL PER THE 2017 FBC SEC. R
 P3111.2.2.
  
 E. PLEASE SHOW THE DOWN-STAIRS WASHING MACHINE ON A
 SANITARY FITTING ABOVE THE NINETY-DEGREE ELBOW PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. PLEASE SHOW ALL LAVS AND SINK ON A SANITARY TEE
 ABOVE GROWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. THERE IS A CROSS TEE FITTING ON THE TWO UPSTAIRS
 BATHROOMS THAT CONNECT TO A KITCHEN SINK AND ANOTHER
 SANITARY DRAIN THAT SEEMS TO BE CONFUSING. PLEASE
 CHANGE TO SHOW CLARITY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  