Plan Review Notes
Plan Review Notes For Permit 20120283
Permit Number 20120283
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-04-01 12:55:13PREVIOUS FIRE COMMENTS WERE NOT SPECIFICALLY ADDRESSED
 AND HAVE BEEN RESUBMITTED BELOW.
  
 IT APPEARS THAT THIS OCCUPANCY IS REQUIRED TO HAVE FIRE
 SPRINKLERS PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE ADDRESS THE FOLLOWING PREVIOUS COMMENTS:
  
 1) FOR CLARIFICATION PURPOSES, IS THIS A NEW
 INSTALLATION OR REPLACING AN EXISTING ONE?
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK.
  
  
 1A) A PREVIOUS FIRE INSPECTION RECORD OF THIS ADDRESS
 WAS CONDUCTED IN 2012 WITH NO ACTIVE BTR OF FILE FOR
 THE CITY.
 THE CURRENT BTR ON RECORD INDICAES A MINIWAREHOUSE AND
 SELF STORAGE.
  
 THIS PERMIT APPEARS TO SUPPORT A WOODWORKING BUSINESS
 WHICH WOULD BE A CHANGE OF OCCUPANCY.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND A CHANGE OF
 OCCUPANCY PERMIT.
  
  
 1B) PER THE CHANGE OF OCCUPANCY AND NFPA 1
  
 13.3.2.28 WOODWORKING OPERATIONS. AN APPROVED AUTOMATIC
 FIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN BUILDINGS
 CONTAINING
 WOODWORKING OPERATIONS EXCEEDING 2500 FT2 (232 M2) THAT
 USE
 EQUIPMENT, MACHINERY, OR APPLIANCES; THAT GENERATE
 FINELY DIVIDED
 COMBUSTIBLE WASTE; OR THAT USE FINELY DIVIDED
 COMBUSTIBLE
 MATERIALS
  
 PLEASE PROVIDE DETAILS AND COMPLY WITH CODE IF
 APPLICABLE SQUARE FOOTAGE.
  
  
  
 2) SHEET M 2 - THERE IS AN INDICATION OF A DUCT RUNNING
 THROUGH A UNIT SEPARATION WALL.
  
 IS THIS WALL A REQUIRED FIRE WALL WHERE A FIRE DAMPER
 IS REQUIRED?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) PERMITS FOR THIS ADDRESS INDICATE A 2ND FLOOR. THE
 SUBMITTED PLANS DO NOT INDICATE A 2ND FLOOR.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO INDICATIONS THAT THE ELECTIAL
 SYSTEM/EQUIPMENT COMPLY WITH NFPA 664 OR NFPA 70
  
  
 7.3 ELECTRICAL SYSTEMS.
 7.3.1 ALL ELECTRICAL SYSTEMS AND SYSTEM COMPONENTS
 SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 70, NATIONAL
 ELECTRICAL CODE.
 7.3.2* PORTIONS OF THE FACILITY WHERE DUST
 ACCUMULATIONS OCCUR
 OR WHERE SUSPENSIONS OF WOOD DUST IN AIR COULD OCCUR
 SHALL BE
 EQUIPPED WITH ELECTRICAL SYSTEMS AND EQUIPMENT PER
 ARTICLE
 502 OR 503 OF NFPA 70, NATIONAL ELECTRICAL CODE.
  
 7.6* LIGHTING. LIGHTING SYSTEM FIXTURES SHALL BE
 DESIGNED, INSTALLED,
 AND MAINTAINED SUCH THAT THEY DO NOT POSE A POTENTIAL
 IGNITION HAZARD DUE TO THE HEAT EVOLVED FROM NORMAL
 OPERATION
 OR AS A RESULT OF CATASTROPHIC FAILURE OR DAMAGE.
  
 PLEASE REVIEW, PROVIDE DETAILS OF COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]