| Date |
Text |
| 2021-04-01 12:55:13 | PREVIOUS FIRE COMMENTS WERE NOT SPECIFICALLY ADDRESSED |
| | AND HAVE BEEN RESUBMITTED BELOW. |
| | |
| | IT APPEARS THAT THIS OCCUPANCY IS REQUIRED TO HAVE FIRE |
| | SPRINKLERS PER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | PLEASE ADDRESS THE FOLLOWING PREVIOUS COMMENTS: |
| | |
| | 1) FOR CLARIFICATION PURPOSES, IS THIS A NEW |
| | INSTALLATION OR REPLACING AN EXISTING ONE? |
| | |
| | PLEASE PROVIDE A DETAILED SCOPE OF WORK. |
| | |
| | |
| | 1A) A PREVIOUS FIRE INSPECTION RECORD OF THIS ADDRESS |
| | WAS CONDUCTED IN 2012 WITH NO ACTIVE BTR OF FILE FOR |
| | THE CITY. |
| | THE CURRENT BTR ON RECORD INDICAES A MINIWAREHOUSE AND |
| | SELF STORAGE. |
| | |
| | THIS PERMIT APPEARS TO SUPPORT A WOODWORKING BUSINESS |
| | WHICH WOULD BE A CHANGE OF OCCUPANCY. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS AND A CHANGE OF |
| | OCCUPANCY PERMIT. |
| | |
| | |
| | 1B) PER THE CHANGE OF OCCUPANCY AND NFPA 1 |
| | |
| | 13.3.2.28 WOODWORKING OPERATIONS. AN APPROVED AUTOMATIC |
| | FIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN BUILDINGS |
| | CONTAINING |
| | WOODWORKING OPERATIONS EXCEEDING 2500 FT2 (232 M2) THAT |
| | USE |
| | EQUIPMENT, MACHINERY, OR APPLIANCES; THAT GENERATE |
| | FINELY DIVIDED |
| | COMBUSTIBLE WASTE; OR THAT USE FINELY DIVIDED |
| | COMBUSTIBLE |
| | MATERIALS |
| | |
| | PLEASE PROVIDE DETAILS AND COMPLY WITH CODE IF |
| | APPLICABLE SQUARE FOOTAGE. |
| | |
| | |
| | |
| | 2) SHEET M 2 - THERE IS AN INDICATION OF A DUCT RUNNING |
| | THROUGH A UNIT SEPARATION WALL. |
| | |
| | IS THIS WALL A REQUIRED FIRE WALL WHERE A FIRE DAMPER |
| | IS REQUIRED? |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 3) PERMITS FOR THIS ADDRESS INDICATE A 2ND FLOOR. THE |
| | SUBMITTED PLANS DO NOT INDICATE A 2ND FLOOR. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS THAT THE ELECTIAL |
| | SYSTEM/EQUIPMENT COMPLY WITH NFPA 664 OR NFPA 70 |
| | |
| | |
| | 7.3 ELECTRICAL SYSTEMS. |
| | 7.3.1 ALL ELECTRICAL SYSTEMS AND SYSTEM COMPONENTS |
| | SHALL BE |
| | INSTALLED IN ACCORDANCE WITH NFPA 70, NATIONAL |
| | ELECTRICAL CODE. |
| | 7.3.2* PORTIONS OF THE FACILITY WHERE DUST |
| | ACCUMULATIONS OCCUR |
| | OR WHERE SUSPENSIONS OF WOOD DUST IN AIR COULD OCCUR |
| | SHALL BE |
| | EQUIPPED WITH ELECTRICAL SYSTEMS AND EQUIPMENT PER |
| | ARTICLE |
| | 502 OR 503 OF NFPA 70, NATIONAL ELECTRICAL CODE. |
| | |
| | 7.6* LIGHTING. LIGHTING SYSTEM FIXTURES SHALL BE |
| | DESIGNED, INSTALLED, |
| | AND MAINTAINED SUCH THAT THEY DO NOT POSE A POTENTIAL |
| | IGNITION HAZARD DUE TO THE HEAT EVOLVED FROM NORMAL |
| | OPERATION |
| | OR AS A RESULT OF CATASTROPHIC FAILURE OR DAMAGE. |
| | |
| | PLEASE REVIEW, PROVIDE DETAILS OF COMPLIANCE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |