Plan Review Notes
Plan Review Notes For Permit 20120266
Permit Number 20120266
Review Stop G
Sequence Number 2
Notes
Date Text
2021-01-25 17:34:0001/25/21 GAS 2ND REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A PERMIT IS REQUIRED FOR GAS BY A LICENSED
 CONTRACTOR PER THE 2017 FBC-PLUMBING SEC.608.1. THIS IS
 NOTED THAT THIS IS NOT THE RESPONSIBILITY OF THE
 ENGINEER AS THESE COMMENTS ARE REQUESTING DOCUMENTATION
 THAT NEED TO BE VERIFIED FOR COMPLIANCE SO CONTRACTOR
 SHALL SUPPLY THEM.
  
 2. SECOND REQUEST, PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL THE
 GAS APPLIANCES (POOL HEATER, DRYER, AND COOKTOP) PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1. THIS IS NOTED
 THAT THIS IS NOT THE RESPONSIBILITY OF THE ENGINEER AS
 THESE COMMENTS ARE REQUESTING DOCUMENTATION THAT NEED
 TO BE VERIFIED FOR COMPLIANCE SO CONTRACTOR SHALL
 SUPPLY THEM.
  
 3. SECOND REQUEST, PLEASE SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC.
 G2421.1. THIS IS NOTED THAT THIS IS NOT THE
 RESPONSIBILITY OF THE ENGINEER AS THESE COMMENTS ARE
 REQUESTING DOCUMENTATION THAT NEED TO BE VERIFIED FOR
 COMPLIANCE SO CONTRACTOR SHALL SUPPLY THEM.
  
 4. SECOND REQUEST PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2 (7), WHERE CONNECTED TO RIGID PIPING, A UNION
 SHALL BE INSTALLED WITHIN 1 FOOT (304 MM) OF EITHER
 SIDE OF THE MP REGULATOR.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  