| Date |
Text |
| 2020-12-18 15:07:48 | 12/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THESE ARE MULTI-FAMILY DWELLINGS, AND THE WATER |
| | USERS WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| | THEIR CONNECTION CONTROL PROGRAM. |
| | |
| | 2. A LICENSED CONTRACTOR MUST REQUIRE SUB PLUMBING AND |
| | GAS PERMITS FOR THE SCOPE OF WORK PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 3. ON SHEET P-3, IN THE MASTER BATH, THE ISOMETRIC |
| | DRAWING SHOWS AN AIR ADMITANVCE VALVE THAT REQUIRES IT |
| | TO BE ACCESSIBLE. IT HAS TO BE IN A BOX WITH A COVER IF |
| | IT IS LOCATED BEHIND THE FREESTANDING TUB. YOU MAY NOT |
| | NEED IT AS THE DISTANCE OF 8' FROM THE LAVS LOOKS |
| | RELATIVELY CLOSE. PLEASE CHANGE, OR IF IT IS BEHIND THE |
| | TUB, PLEASE NOTE THE PLANS FOR AN ACCESSIBLE LOCATION |
| | PER THE 2017 FBC SEC. R 3114.5. |
| | |
| | 4. ON SHEET P-2, THE WASHING MACHINE SHUT OFF VALVES |
| | SHALL BE ACCESSIBLE WITHOUT MOVING THE UNITS AND WITHIN |
| | REACH; PLEASE SHOW TO THE SIDE PER THE 2017 FBC SEC. R |
| | 2903.9.3. |
| | |
| | 5. SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE |
| | REPAIR'S WIDTH, THE CONCRETE'S MINIMUM THICKNESS TO BE |
| | REPLACED, AND THE CONCRETE'S PSI. SHOW THE DOWELS' SIZE |
| | AND LENGTH, THE MINIMUM EMBEDMENT DEPTH INTO THE |
| | EXISTING SLAB, AND THE DOWELS' SPACING IN THE CENTER. |
| | THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE |
| | SOIL AND THE REQUIRED VAPOR BARRIER OVER THE SOIL. A |
| | COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A |
| | FINAL INSPECTION. |
| | |
| | 6. ON SHEET P-4, THE WATER HEATER PAN DRAIN TO THE |
| | OUTSIDE NEEDS TO BE RODENT-PROOF WITH SOME MESH AT THE |
| | EXTERIOR. PLEASE ADD A NOTE TO THE DETAIL TO PROTECT |
| | FROM RODENT INFILTRATION PER THE 2017 FBC SEC. R |
| | 2606.1. |
| | |
| | 7. THERE IS A DETAIL FOR A THERMOSTATIC VALVE ON THAT |
| | SAME PAGE. IT IS NOT REQUIRED ONLY IN THE FREESTANDING |
| | TUB; ONLY THE VALVE DOES NOT COMPLY WITH ASSE 1016/ASME |
| | A112.1016/CSA B125.16 PER THE 2017 FBC SEC. R 2713.3. |
| | |
| | 8. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| | ASKING FOR THE FORM. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |