Plan Review Notes
Plan Review Notes For Permit 20120266
Permit Number 20120266
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-18 15:07:4812/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THESE ARE MULTI-FAMILY DWELLINGS, AND THE WATER
 USERS WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 2. A LICENSED CONTRACTOR MUST REQUIRE SUB PLUMBING AND
 GAS PERMITS FOR THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 3. ON SHEET P-3, IN THE MASTER BATH, THE ISOMETRIC
 DRAWING SHOWS AN AIR ADMITANVCE VALVE THAT REQUIRES IT
 TO BE ACCESSIBLE. IT HAS TO BE IN A BOX WITH A COVER IF
 IT IS LOCATED BEHIND THE FREESTANDING TUB. YOU MAY NOT
 NEED IT AS THE DISTANCE OF 8' FROM THE LAVS LOOKS
 RELATIVELY CLOSE. PLEASE CHANGE, OR IF IT IS BEHIND THE
 TUB, PLEASE NOTE THE PLANS FOR AN ACCESSIBLE LOCATION
 PER THE 2017 FBC SEC. R 3114.5.
  
 4. ON SHEET P-2, THE WASHING MACHINE SHUT OFF VALVES
 SHALL BE ACCESSIBLE WITHOUT MOVING THE UNITS AND WITHIN
 REACH; PLEASE SHOW TO THE SIDE PER THE 2017 FBC SEC. R
 2903.9.3.
  
 5. SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 REPAIR'S WIDTH, THE CONCRETE'S MINIMUM THICKNESS TO BE
 REPLACED, AND THE CONCRETE'S PSI. SHOW THE DOWELS' SIZE
 AND LENGTH, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, AND THE DOWELS' SPACING IN THE CENTER.
 THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE
 SOIL AND THE REQUIRED VAPOR BARRIER OVER THE SOIL. A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A
 FINAL INSPECTION.
  
 6. ON SHEET P-4, THE WATER HEATER PAN DRAIN TO THE
 OUTSIDE NEEDS TO BE RODENT-PROOF WITH SOME MESH AT THE
 EXTERIOR. PLEASE ADD A NOTE TO THE DETAIL TO PROTECT
 FROM RODENT INFILTRATION PER THE 2017 FBC SEC. R
 2606.1.
  
 7. THERE IS A DETAIL FOR A THERMOSTATIC VALVE ON THAT
 SAME PAGE. IT IS NOT REQUIRED ONLY IN THE FREESTANDING
 TUB; ONLY THE VALVE DOES NOT COMPLY WITH ASSE 1016/ASME
 A112.1016/CSA B125.16 PER THE 2017 FBC SEC. R 2713.3.
  
 8. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved