Plan Review Notes
Plan Review Notes For Permit 20120266
Permit Number 20120266
Review Stop G
Sequence Number 1
Notes
Date Text
2020-12-18 16:49:4912/18/20 GAS 1ST REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A PERMIT IS REQUIRED FOR GAS BY A LICENSED
 CONTRACTOR PER THE 2017 FBC-PLUMBING SEC.608.1.
  
 2. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL THE GAS APPLIANCES
 (POOL HEATER, DRYER, AND COOKTOP) PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. THE GAS HEATER IS NOT SHOWN ON THE GAS ISOMETRIC,
 BUT THERE IS A DIFFERENCE OF 180 BTU ON THE GAS
 CALCULATION. PLEASE ESTABLISH BTU'S SCHEDULE AND
 INCLUDE ALL GAS APPLIANCES PER THE 2017 FBC RES. SEC.
 G2413.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS), OR 2017 FBC
 RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE ISOMETRIC PLAN PER THE 2017 FBC RES. SEC.
 G2413.2.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 7. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 8. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 9. THE GAS DRYER'S VALVE IS BEHIND THE STACKABLE UNITS,
 AND THEY SHALL BE READILY ACCESSIBLE WITHOUT MOVING THE
 UNITS PER THE 2017 FBC FG SEC. DEFINITIONS ACCESS.
  
 10. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  