| 2020-12-18 16:49:49 | 12/18/20 GAS 1ST REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A PERMIT IS REQUIRED FOR GAS BY A LICENSED |
| | CONTRACTOR PER THE 2017 FBC-PLUMBING SEC.608.1. |
| | |
| | 2. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL THE GAS APPLIANCES |
| | (POOL HEATER, DRYER, AND COOKTOP) PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 3. THE GAS HEATER IS NOT SHOWN ON THE GAS ISOMETRIC, |
| | BUT THERE IS A DIFFERENCE OF 180 BTU ON THE GAS |
| | CALCULATION. PLEASE ESTABLISH BTU'S SCHEDULE AND |
| | INCLUDE ALL GAS APPLIANCES PER THE 2017 FBC RES. SEC. |
| | G2413. |
| | |
| | 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS), OR 2017 FBC |
| | RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE ISOMETRIC PLAN PER THE 2017 FBC RES. SEC. |
| | G2413.2. |
| | |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | |
| | 7. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| | |
| | 8. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 9. THE GAS DRYER'S VALVE IS BEHIND THE STACKABLE UNITS, |
| | AND THEY SHALL BE READILY ACCESSIBLE WITHOUT MOVING THE |
| | UNITS PER THE 2017 FBC FG SEC. DEFINITIONS ACCESS. |
| | |
| | 10. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| | ASKING FOR THE FORM. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |