| 2021-01-06 10:49:50 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20120261 |
| | ADD: 1400 CENTRREPARK BLVD. # 400 |
| | CONT: CHANDLER CONSTRUCTION CO. |
| | TEL: 561-791-6934 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 16TH/ 2020 |
| | ACTION: DENIED |
| | NOTE THERE WERE NO CHANGES TO THE PLANS, PLAN INCOMING |
| | DATE 12/04/2020, NO REFERENCE TO PLANS BEING UPDATED. |
| | HERE IS ALSO NO RESPONSE LETTER FROM THE DESIGNER OF |
| | RECORD. |
| | |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B). WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) 2ND REQUEST. SHEET A-2 IN THE COFFEE ROOM LABELED |
| | 403 THERE ARE (2) NOTES, NOTE 3 INDICATES THE EXISTING |
| | MILLWORK (BASE CABINET IS TO REMAIN AND NOTE (4) TO ADD |
| | A NEW SINK. THE FLOOR PLAN REFERENCES A DETAIL 7 SHEET |
| | A-3. THIS DETAIL IS A ELEVATION VIEW OF THE EXISTING |
| | BASE CABINET, CABINET HEIGHT IS GIVEN AT 34 INCHES. |
| | THERE ARE NO REFERENCES AS TO EITHER A FRONT APPROACH |
| | OR SIDE APPROACH IS INTENDED AND COMPLIANCE WITH THE |
| | 2017 ACCESSIBILITY CODE SECTIONS: |
| | |
| | SINKS> 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED |
| | CLEAR FLOOR SPACE ON THE FLOOR PLAN. |
| | |
| | 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY & |
| | DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. |
| | |
| | 2) 2ND REQUEST. SHEET A-2 VERSES SHEET A-5. SHEET A-2 |
| | FLOOR PLAN DOES NOT SHOW THE PROBLEM THAT THE FURNITURE |
| | PLAN DOES ON SHEET A-5. |
| | SHEET A-5 JUST ABOUT EVERY WALLED OFFICE ON THE |
| | EXTERIOR OF THE BUILDING AND OFFICE 424-432, ALL DOORS |
| | SWING INTO THE OFFICES, IN SOME CASES AS DRAWN THE DOOR |
| | CAN NOT OPEN WITH HITTING THE FURNITURE THE OFFICES DO |
| | NOT SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY |
| | CODE SECTION ACCESS. CODE 404.2.4 MANEUVERING |
| | CLEARANCES. DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE FOR SIDE CLEARANCE. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |