| 2020-12-10 16:36:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE ARE PULL STATIONS LOCATED THROUGHOUT THE |
| | OCCUPANCY. |
| | |
| | PER NFPA 101, CH 30 AND CH 9 PULLS STATIONS ARE NOT |
| | SPECIFICALLY REQUIRED: |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR |
| | WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE |
| | MEETING THE |
| | REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A |
| | FIRE ALARM |
| | SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS |
| | MODIFIED BY |
| | 30.3.4.2 THROUGH 30.3.4.5. |
| | |
| | 30.3.4.2 INITIATION. |
| | 30.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE BY |
| | MANUAL MEANS IN ACCORDANCE WITH 9.6.2, UNLESS THE |
| | BUILDING |
| | COMPLIES WITH 30.3.4.2.2. |
| | |
| | 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 30.3.5, |
| | REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON |
| | OPERATION OF |
| | THE AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 9.6.2 SIGNAL INITIATION. |
| | 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, |
| | ACTUATION |
| | OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF |
| | THE FOLLOWING |
| | MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH |
| | MEANS: |
| | (1) MANUAL FIRE ALARM INITIATION |
| | (2) AUTOMATIC DETECTION |
| | (3) EXTINGUISHING SYSTEM OPERATION |
| | |
| | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| | DETECTION OR |
| | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| | ONE MANUAL |
| | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| | HAVING |
| | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| | ALARM SIGNAL. |
| | |
| | IN AN INTENT TO REDUCE FALSE ALARMS OR UNLESS |
| | SPECIFCALLY REQUIRED BY THE EOR OR OWNER, PULL STATIONS |
| | THROUGHOUT ARE NOT REQUIRED AND CAN BE REMOVED ON EACH |
| | FLOOR EXCEPT AT THE FACP LOCATION. |
| | |
| | 2) THERE ARE SMOKE DETECTORS LOCATED THROUGHOUT THE |
| | OCCUPANCY. |
| | |
| | PER NFPA 101, CH 30 AND CH 9 SMOKE DETECTION DEVICES |
| | ARE NOT SPECIFICALLY REQUIRED: |
| | |
| | 30.3.4.4 DETECTION. (RESERVED) |
| | 30.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED |
| | IN |
| | ACCORDANCE WITH 9.6.2.10 IN EVERY SLEEPING AREA, |
| | OUTSIDE EVERY |
| | SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE |
| | BEDROOMS, AND ON |
| | ALL LEVELS OF THE DWELLING UNIT, INCLUDING BASEMENTS. |
| | |
| | IN AN INTENT TO REDUCE FALSE ALARMS OR UNLESS |
| | SPECIFCALLY REQUIRED BY THE EOR OR OWNER PULL STATIONS |
| | CAN BE REMOVED ON EACH FLOOR |
| | |
| | |
| | 3) THERE ARE INDICATIONS CARD READERS/ACCESS CONTROL |
| | INSTALLATION SHALL BE SUBMITTED UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS. |
| | |
| | INSTALLATION SHALL COMPLY WITH NFPA 101, CH 7 MEANS OF |
| | EGRESS AS APPLICABLE. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 4) THE FIRE ALARM PANEL (FACP) COULD NOT BE LOCATED ON |
| | THE FLOOR PLAN SHEETS. |
| | |
| | PLEASE REVIEW AND CORRECT OR BETTER DEFINE ITS |
| | LOCATION. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |