| Plan Review Notes For Permit 20120242 |
| Permit Number |
20120242 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-28 08:07:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE OF WORK SHOWN IS LOW FOR THE AMOUNT OF | | | FIXTURES SHOWN PLEASE SUBMIT A SIGNED CONTRACT SHOWING | | | BREAK DOWN OF FIXTURES AND LABOR. | | | | | | 2) PLEASE INDICATE THE AMOUNT OF EACH TYPE OF FIXTURE | | | BEING USED. | | | | | | 3) NO CIRCUITRY SHOWN FOR LIGHTING PLEASE INDICATE ON | | | DRAWINGS. SIZE OF CIECUIT SIZE OF WIRE TO BE USED. |
|