| 2020-12-15 15:47:34 | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) PROVIDE RISER DIAGRAM SHOWING SIZE OF MAIN AND SIZE |
| | OF CONDUCTORS 215.5 NEC |
| | |
| | PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| | BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL. |
| | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| | 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC 107.2.1 |
| | |
| | 2) PROVIDE PANEL SCHEDULE SHOWING SIZE OF CIRCUIT AND |
| | BREAKER SIZE. |
| | |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| | RE3706.2, RE3902 |
| | |
| | 3) PROVIDE LOAD CALCULATION PER ARTICLE 220 NEC |
| | |
| | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS |