| Date |
Text |
| 2021-06-03 10:39:47 | 06/03/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THIS IS THE SECOND, SO PLEASE PROVIDE A DETAILED |
| | NARRATIVE OF THE SCOPE OF WORK THAT IS BEING DONE. THE |
| | PERMIT SAYS WHAT YOU ARE TRYING TO DO, BUT IF YOU ARE |
| | MOVING OR ADDING, IS IT IN A NEW STRUCTURE OR ANOTHER |
| | PART OF THE HOUSE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 101.2. |
| | |
| | 2. PLEASE PROVIDE DETAILED PLANS AND DOCUMENTS FOR THE |
| | WORK BEING DONE. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS, AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5) PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THERE IS NO VALUE LISTED ON THE PLUMBING |
| | SUB-APPLICATION, AND THE OVERALL VALUE IS LOW. WPB |
| | AMENDMENTS TO THE FBC 109.3 BUILDING PERMITS |
| | VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, THE VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COSTS, OVERHEAD, AND PROFIT, EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| | PUBLISHED BY INTERNATIONAL CODE CONGRESS. THE FINAL |
| | BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. A MAIN BUILDING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 6. TWO SEPARATE ISOMETRIC DRAWINGS SUBMITTED FOR THE |
| | SANITARY, PLEASE COMBINE INTO ONE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 7. PLEASE PROVIDE WATER SOURCE ON THE SCOPE OF WORK |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. PLEASE SHOW THE DIMENSION BETWEEN FIXTURES |
| | INSTALLATION TO CONFORM TO THE 2017 FBC SEC. R 2705.1 |
| | (5) AND R 2708.1 GENERAL. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |