Plan Review Notes
Plan Review Notes For Permit 20120238
Permit Number 20120238
Review Stop M
Sequence Number 3
Notes
Date Text
2021-06-10 17:09:581) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING ANY DUCT
 WORK BEING REWORKED OR ADDED. FBC 107.2.1
 2) PLEASE SHOW HOW THE NEW BATHROOM WILL BE VENTILATED.
 FBC RES TABLE M1507.4
  