2021-01-11 16:37:54GUARDRAIL SUBMITTAL, THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 *****NOTE:
 ALL THE COMMENTS FROM FIRST REVIEW STILL APPLY.
 REQUESTED INFORMATION WAS NOT PROVIDED.
  
 ONLY THE ENGINEER GUARDRAIL CALCULATIONS WERE
 RESUBMITTED. THEY DON'T SEEM TO BE REVISED. SAME
 CALCULATIONS WERE RESUBMITTED. THE ONLY INFORMATION
 THAT WAS CHANGED WAS THE "CHECKED BY AND THE DATES.
 ALSO, IT IS NOT CLEAR WHY THE
 DATES WERE CHANGED AND NOW THEY SHOW AN EARLIER DATE
 THAN THE ONE PREVIOUSLY SUBMITTED.
 ENGINEER PROVIDING THE CALCULATIONS TO CLARIFY.
  
  
  
  
 ENGINEERS/ARCHITECTS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- GUARDRAIL DRAWINGS WERE UPLOADED TO PROJECTDOX AS A
 SINGLE PDF. ALL DRAWINGS NEED TO BE UPLOADED
 INDIVIDUALLY IN THE DRAWINGS FOLDER AS REQUIRED BY THE
 CITY GUIDE FOR DIGITAL PLAN REVIEW. ALSO, DRAWINGS NEED
 TO FOLLOW THE FILE NAMING GUIDELINES. SEE THE CITY
 QUICK START GUIDE: DIGITAL PLAN REVIEW.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS ABOUT
 THIS.
  
 2- SHEET F-1:
 A)REVISE THE APPLICABLE CODES. "THE ALUMINUM DESIGN
 MANUAL 2015" CAN NOT BE USED FOR THIS PROJECT. THE
 ALUMINUM DESIGN MANUAL IS NOT FOR GUARDRAILS. ALSO,
 THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING GARAGE
 NOT IN A RESIDENTIAL BUILDING. THIS IS A VEHICLE
 BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE WITH
 SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3
 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE UNDER WHICH THE MASTER PERMIT WAS
 ISSUED IS THE FLORIDA BUILDING CODE SIXTH EDITION
 (2017) NOT FBC 2020. CHAPTER 553 F.S. REVISE AS
 REQUIRED.
  
 3- SHEET F-2:
 A) REVISE THE DESIGN LOADS AND ALUMINUM NOTES. SEE ITEM
 #2 ABOVE. NEED TO COMPLY WITH SEC. 4.5.3 OF ASCE 7-10
 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH EDITION (2017).
  
 4-REVISE SHEETS F-3 THRU F-7 TO COMPLY WITH SEC. 4.5.3
 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH
 EDITION (2017).
  
 5- ENGINEER TO REVISE CALCULATIONS SUBMITTED:
 A) THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING
 GARAGE NOT IN A RESIDENTIAL BUILDING (R-2). THIS IS A
 VEHICLE BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE
 WITH SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC.
 1607.8.3 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE IS THE FLORIDA BUILDING CODE SIXTH
 EDITION (2017) NOT FBC 2020.
 CHAPTER 553 F.S.
  
 6- REVISED DRAWINGS AND CALCULATIONS TO BE
 REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD
 PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4 CITY
 AMENDMENTS.
  
 7- DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  