| Date |
Text |
| 2020-12-18 11:55:41 | 2ND REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20120214 |
| | 12/18/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | COMMENTS FROM THE 1ST REVIEW ARE MARKED AS PASSED OR |
| | FAILED. PLEASE SEE NOTES ADDED TO FAILED COMMENTS. THE |
| | REQUESTED RESPONSE NARRATIVE WAS NOT PROVIDED. |
| | |
| | 1) FAILED. SHEET P101A: PLEASE PROVIDE A COMPLETE GAS |
| | RISER DRAWING SHOWING THE NEW AND EXISTING PIPING AND |
| | NEW AND EXISTING GAS LOADS REQUIRED BY SECTION |
| | 107.3.5.3 WPB, AND SECTIONS 401.3 & 401.4 FBC FG. |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE RISER- |
| | FBC-17 FG. SHEET P304: THE NEW PLAN SHEET SHOWS PARTIAL |
| | RISERS FOR THE WATER HEATERS IN THE ADULT AND AND THE |
| | CHILD/ADOLESCENT. COMPLETE GAS RISER NOT PROVIDED. |
| | |
| | A) FAILED. DELIVERY PRESSURE AT THE METER- SECTIONS |
| | 402.1, 402.6. NOT PROVIDED. GAS SYSTEM PRESSURE NOT |
| | SHOWN ON P303. |
| | |
| | B) FAILED. TYPES AND SIZES OF GAS PIPING- SECTIONS |
| | 402.3 & 403.1. TYPES OF PIPING NOT SHOWN ON P304. |
| | |
| | C) FAILED. TOTAL DEVELOPED LENGTH OF THE PIPING FROM |
| | THE METER TO THE MOST REMOTE GAS OUTLET- SECTION |
| | 402.4.1`. PARTIAL RISER LENGTHS SHOWN ON P304. |
| | |
| | D) PASSED. BRANCH AND CUT PIPING LENGTHS-SECTION |
| | 402.4.2. |
| | |
| | E) FAILED. INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL |
| | LOAD OF THE SYSTEM- SECTION 402.2. INDIVIDUAL LOADS |
| | SHOWN, TOTAL LOAD NOT SHOWN ON P304. |
| | |
| | F) FAILED. LOCATIONS OF REGULATORS AND OUTLET |
| | PRESSURES- SECTIONS 410.1 & 410.2. THERE IS A NOTE ON |
| | THE PLAN SPECIFYING A PRV'S FOR THE GAS PIPING TO THE |
| | WATER HEATERS. IS THIS VALVE TO BE INSTALLED IN |
| | ADDITION TO GAS REGULATORS WHICH ARE TYPICALLY USED TO |
| | REDUCE PRESSURE? REGULATOR LOCATIONS, INPUT AND OUTPUT |
| | PRESSURES NOT SHOWN ON P304. |
| | |
| | G) FAILED. PIPE SIZING TABLES- SECTION 402.4. NOT |
| | PROVIDED. |
| | |
| | 2) PASSED. P101A: PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE WATER HEATER AND METHOD OF PROVIDING THE AIR- |
| | SECTION 304.1 & 624.1 FBC FG. |
| | |
| | 3) PASSED. P101A: PROVIDE VENTING SPECIFICATIONS AND |
| | DIAGRAMS FOR THE GAS-FIRED WATER HEATERS- SECTIONS |
| | 501.1 & 624.1 FBC FG. SHOW THE TYPE AND SIZE OF VENTS, |
| | VENT RUNS AND TERMINATION LOCATIONS. |
| | |
| | 4) PASSED. PI0IA: PROVIDE VENTING DIAGRAMS FOR THE |
| | PRVS. SHOW THE TYPE AND SIZE OF VENTS, VENT RUNS AND |
| | TERMINATION LOCATIONS- SECTIONS 410.3 & 410.3.1 FBC FG. |
| | |
| | 5) PASSED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATER HEATERS- SECTION 624.1 FBC FG. |
| | |
| | 6) FAILED. PLEASE ADJUST THE $2000.00 VALUE FOR |
| | INSTALLATION OF THE WATER HEATERS TO INCLUDE THE COST |
| | OF THE WATER HEATERS AND ALL OTHER APPURTENANCES SUCH |
| | AS THE VENTING- SECTIONS 109.3 WPB. PERMIT VALUE IS |
| | BASED ON LABOR, MATERIALS, EQUIPMENT, APPLIANCES, |
| | DESIGN FEES AND SITE WORK. PLEASE PROVIDE A COPY OF A |
| | SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES TO VERIFY |
| | TOTAL COSTS. NO DOCUMENTATION SUBMITTED OR RESPONSE |
| | MADE TO THE COMMENT. |
| | |
| | NEW COMMENT. |
| | |
| | 1) THE NEW SUBMITTED PLANS SHEETS- M101A, P001, P002, |
| | P304 HAVE COPIED ENGINEER?S SEALS AND SIGNATURES. THEY |
| | ARE PAPER COPIES. PLEASE NOTE THAT ELECTRONICALLY |
| | TRANSMITTED PLAMNS SHALL BEAR THE DIGITAL SIGNATURES OF |
| | THE ENGINEER OF RECORD- FL. STATUTE 471.025, AND |
| | SECTION 61G15-23.005 FAC. PLEASE SEE SIGNATURE FOR |
| | ADDITIONAL INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |