2020-12-14 10:08:041ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20120214
 12/14/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THAT THE FUEL
 GAS REVIEW AND COMPLIANCES FOR PERMITTING WERE REMOVED
 UNDER PERMIT 18120436. NO REVIEWS WERE PERFORMED.
  
 1) SHEET P101A: PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING SHOWING THE NEW AND EXISTING PIPING AND NEW AND
 EXISTING GAS LOADS REQUIRED BY SECTION 107.3.5.3 WPB,
 AND SECTIONS 401.3 & 401.4 FBC FG. PLEASE PROVIDE THE
 FOLLOWING INFORMATION ON THE RISER- FBC-17 FG.
 A) DELIVERY PRESSURE AT THE METER- SECTIONS 402.1,
 402.6.
 B) TYPES AND SIZES OF GAS PIPING- SECTIONS 402.3 &
 403.1
 C) TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER
 TO THE MOST REMOTE GAS OUTLET- SECTION 402.4.1`.
 D) BRANCH AND CUT PIPING LENGTHS-SECTION 402.4.2.
 E) INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL LOAD OF
 THE SYSTEM- SECTION 402.2
 F) LOCATIONS OF REGULATORS AND OUTLET PRESSURES-
 SECTIONS 410.1 & 410.2. THERE IS A NOTE ON THE PLAN
 SPECIFYING A PRV'S FOR THE GAS PIPING TO THE WATER
 HEATERS. IS THIS VALVER TO BE INSTALLED IN ADDITON TO
 GAS REGULATORS WHICH ARE TYPICALLY USED TO REDUCE
 PRESSURE?
 G) PIPE SIZING TABLES- SECTION 402.4.
  
 2) P101A: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 WATER HEATER AND METHOD OF PROVIDING THE AIR- SECTION
 304.1 & 624.1 FBC FG.
  
 3) P101A: PROVIDE VENTING SPECIFICATRIONS AND DIAGRAMS
 FOR THE GAS-FIRED WATER HEATERS- SECTIONS 501.1 & 624.1
 FBC FG. SHOW THE TYPE AND SIZE OF VENTS, VENT RUNS AND
 TERMINATION LOCATIONS-
  
 4) PI0IA: PROVIDE VENTING DIAGRAMS FOR THE PRVS. SHOW
 THE TYPE AND SIZE OF VENTS, VENT RUNS AND TERMINATION
 LOCATIONS- SECTIONS 410.3 & 410.3.1 FBC FG.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATERS- SECTION 624.1 FBC FG.
  
 6) PLEASE ADJUST THE $2000.00 VALUE FOR INSTALLATION OF
 THE WATER HEATERS TO INCLUDE THE COST OF THE WATER
 HEATERS AND ALL OTHER APPURTENANCES SUCH AS THE
 VENTING- SECTIONS 109.3 WPB. PERMIT VALUE IS BASED ON
 LABOR, MATERIALS, EQUIPMENT, APPLIANCES, DESIGN FEES
 AND SITE WORK. PLEASE PROVIDE A COPY OF A SIGNED
 CONTRACT AND/OR ESTIMATES AND INVOICES TO VERIFY TOTAL
 COSTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  