Plan Review Notes
Plan Review Notes For Permit 20120209
Permit Number 20120209
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-11 13:46:35PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
 FEMA NFIP
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: FINISHED CONSTRUCTION ELEVATION CERTIFICATE (EC)
  
 FINAL EC REVIEW CHECKLIST
  
 1) VERIFY BFE - BFE 7.0 NAVD PER MY GEO NAV.
 2) VERIFY EC IS SIGNED AND SEALED BY SURVEYOR - SIGNED
 AND SEALED BY SURVEYOR
 3) VERIFY FLOOD VENTS ARE LOCATED ON FLOOR
 PLAN/FOUNDATION - 4 SMART VENTS PROPOSED ON FLOOR PLAN
 4) VERIFY PRODUCT APPROVALS AND ICC-ES REPORT FOR SMART
 VENTS HAVE BEEN SUBMITTED FOR REVIEW - CANNOT LOCATE
 5) VERIFY FINISHED FLOOR ELEVATION (DFE) ON
 FOUNDATION/FLOOR PLAN - FF ELVATION (MAIN HOUSE) - 9.6
 FEET NAVD, FF (GARAGE) - 8.4 FEET NAVD
 6) REVIEW FINISHED CONSTRUCTION EC PER FEMA NFIP EC AND
 INSTRUCTIONS 2019 ED. AND CITY ORDINANCE NO. 4658-16.
  
 EC REVIEW COMMENTS:
  
 1. SECTION A9. NUMBER OF FLOOD OPENINGS - 8.
 PHOTOGRAPHS SHOW 4 OPENINGS WITH TWO VENTS EACH. PLANS
 SHOW 4 SMART VENTS SHALL BE INSTALLED. PLEASE CLARIFY.
 REVISION TO PLANS MAY BE REQUIRED.
 2. ATTACH A COPY OF THE INDIVIDUAL ENGINEERED FLOOD
 OPENING CERTIFICATION OR AN EVALUATION REPORT ISSUED BY
 THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE
 (ICC-ES).
 3. PROVIDE PRODUCT APPROVALS FOR PROPOSED SMART VENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  