| 2020-12-11 13:46:35 | PLAN REVIEW / NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | FEMA NFIP |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | RE: FINISHED CONSTRUCTION ELEVATION CERTIFICATE (EC) |
| | |
| | FINAL EC REVIEW CHECKLIST |
| | |
| | 1) VERIFY BFE - BFE 7.0 NAVD PER MY GEO NAV. |
| | 2) VERIFY EC IS SIGNED AND SEALED BY SURVEYOR - SIGNED |
| | AND SEALED BY SURVEYOR |
| | 3) VERIFY FLOOD VENTS ARE LOCATED ON FLOOR |
| | PLAN/FOUNDATION - 4 SMART VENTS PROPOSED ON FLOOR PLAN |
| | 4) VERIFY PRODUCT APPROVALS AND ICC-ES REPORT FOR SMART |
| | VENTS HAVE BEEN SUBMITTED FOR REVIEW - CANNOT LOCATE |
| | 5) VERIFY FINISHED FLOOR ELEVATION (DFE) ON |
| | FOUNDATION/FLOOR PLAN - FF ELVATION (MAIN HOUSE) - 9.6 |
| | FEET NAVD, FF (GARAGE) - 8.4 FEET NAVD |
| | 6) REVIEW FINISHED CONSTRUCTION EC PER FEMA NFIP EC AND |
| | INSTRUCTIONS 2019 ED. AND CITY ORDINANCE NO. 4658-16. |
| | |
| | EC REVIEW COMMENTS: |
| | |
| | 1. SECTION A9. NUMBER OF FLOOD OPENINGS - 8. |
| | PHOTOGRAPHS SHOW 4 OPENINGS WITH TWO VENTS EACH. PLANS |
| | SHOW 4 SMART VENTS SHALL BE INSTALLED. PLEASE CLARIFY. |
| | REVISION TO PLANS MAY BE REQUIRED. |
| | 2. ATTACH A COPY OF THE INDIVIDUAL ENGINEERED FLOOD |
| | OPENING CERTIFICATION OR AN EVALUATION REPORT ISSUED BY |
| | THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE |
| | (ICC-ES). |
| | 3. PROVIDE PRODUCT APPROVALS FOR PROPOSED SMART VENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |