| Plan Review Notes For Permit 20120188 |
| Permit Number |
20120188 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-12-31 08:05:01 | FENCE/GATE SHOP DRAWINGS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) SHOP DRAWINGS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD. FBC WPB | | | 107.3.4.1 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL | | | BE SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED | | | AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF | | | THE BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE | | | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN | | | APPROVED BY THE BUILDING OFFICIAL. | | | |
|