| 2021-04-29 08:31:03 | FAILED |
| | |
| | PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| | |
| | 1) THANK YOU FOR PROVIDING THE GRAPHIC SHOWING HOW THE |
| | SIDEWALK CONNECTION TO THE PUBLIC RIGHT-OF-WAY WILL BE |
| | PROVIDED TO THE THREE BUILDINGS THAT WILL REMAIN ON THE |
| | SITE BOTH DURING CONSTRUCTION AND PRIOR TO THE START OF |
| | CONSTRUCTION OF PHASE II. ZONING REVIEWED YOUR PROPOSED |
| | PLAN WITH ROBERT BROWN, CHIEF BUILDING OFFICIAL, AND IT |
| | IS NOT APPROVED AS SHOWN. YOU MUST CLEARLY SHOW HOW A |
| | PEDESTRIAN, INCLUDING ONE COVERED BY THE ADA, CAN |
| | SAFELY TRAVERSE FROM THE EXISTING SIDEWALK ON THE |
| | MORSELIFE SIDE OF THE SITE TO THE EXISTING SIDEWALK |
| | SERVING THE HOMESAFE BUILDINGS. THE ARROWS THAT ARE |
| | SHOWN ON THE PLAN FORCE THE PEDESTRIAN TO SHARE DRIVE |
| | LANES WITH VEHICLES, WHICH IS NOT PERMITTED. THE |
| | PEDESTRIAN MUST BE ABLE TO USE A SIDEWALK OR HAVE A |
| | PATH THAT IS SEPARATED FROM THE VEHICULAR TRAVEL LANES. |
| | NOTE: THE MINIMUM TRAVEL LANE WIDTH IS 20 FEET FOR FIRE |
| | DEPARTMENT ACCESS, SO THE PROPOSED 20 FOOT WIDE |
| | CONNECTION CANNOT BE NARROWED. THE PEDESTRIAN ROUTE |
| | MUST BE IN PLACE PRIOR TO THE FENCING OF THE |
| | CONSTRUCTION SITE. |
| | |
| | 2) EVEN THOUGH A SEPARATE SITE LIGHTING PERMIT, WITH |
| | PLANS, IS REQUIRED, ZONING NOTED THAT THE ELECTRICAL |
| | REVIEWER HAD ADDED A PASS STAMP TO SHEET E 0-1-1 THE |
| | ELECTRICAL SITE PLAN AND THUS REVIEWED THE PLAN. ZONING |
| | WILL NOT APPROVE THE PROPOSED PLAN. |
| | |
| | A. THE UNDERGROUND DUCT BANK LINES (HIGHLIGHTED BY THE |
| | GREEN BOXES ON THE ELECTRONIC VERSION OF THE PLAN) MUST |
| | BE MOVED OUT OF THE LANDSCAPE AREAS AS THEY DIRECTLY |
| | CONFLICT WITH APPROVED TREE LOCATIONS. THEY CAN BE RUN |
| | UNDER THE PAVEMENT. |
| | |
| | B. THE DUCT BANKS ARE SHOWN COVERED BY COMPACTED EARTH, |
| | WHICH IS NOT PERMITTED IN THE LANDSCAPE AREAS. THE TREE |
| | ROOTS WILL NOT PROPERLY GROW IN COMPACTED EARTH. |
| | ADDITIONALLY, THE TREES NEED A FULL THREE FEET OF COVER |
| | FOR PROPER ROOT GROWTH, WHICH DOES NOT OCCUR DUE TO THE |
| | INSTALLATION OF THE MYLAR WARNING TAPE AT TWO FEET IN |
| | DEPTH. |
| | |
| | 3) SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR THE |
| | FOLLOWING: |
| | |
| | A. SITE LIGHTING |
| | B. BICYCLE RACKS |
| | C. HARDSCAPE |
| | D. PARKING LOT STRIPING |
| | E. PERIMETER WALLS AND FENCES |
| | |