| 2021-04-12 12:19:28 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120145 |
| | 4/12/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST AND 2ND REVIEW LISTED BELOW HAVE |
| | NOT BEEN COMPLETELY RESOLVED. NOTES HAVE BEEN ADDED FOR |
| | FURTHER CLARIFICATION. |
| | |
| | 3) FAILED. A1.6.1 & P DRAWINGS: BASED ON THE SERVING |
| | KITCHEN PLAN IT APPEARS THAT A GREASE INTERCEPTOR MUST |
| | BE PROVIDED TO RECEIVE THE DRAINAGE FROM THE HOT FOOD |
| | WELL, DISHWASHER, FOOD WASTE DISPOSAL, AND ALL DIRECT |
| | OR INDIRECT WASTE RECEPTORS SERVING KITCHEN APPLIANCES |
| | AND EQUIPMENT THAT PRODUCE GREASE OR FAT-LADEN WASTE |
| | EFFLUENTS- SEE SECTION 1003.3.1 FBC P. CONCERNING THE |
| | FOOD WASTE DISPOSAL REFER TO SECTION 1003.3.2 FBC P AND |
| | PROVIDE A SOLIDS INTERCEPTOR TO SEPARATE THE DISCHARGE |
| | BEFORE CONNECTING TO THE INTERCEPTOR. SHEETS P2.1.1 & |
| | P4.1.1: THE ARCHITECT'S RESPONSE INDICATES A GREASE |
| | INTERCEPTOR TO BE INSTALLED UNDER THE KITCHEN SINK |
| | HOWEVER NOTE 8 ON SHEET P.2.1.1 SPECIFIES A SOLIDS |
| | INTERCEPTOR EQUAL TO STRIEM MODEL #HTL-1176-1. PLEASE |
| | NOTE THAT HTL-1176-1 IS A HAIR AND LINT INTERCEPTOR. |
| | PLEASE PROVIDE THE CORRECT INTERCEPTOR MAKE AND MODEL |
| | AND SUBMIT MANUFACTURER'S SPECIFICATIONS. SOLIDS |
| | INTERECPTORS ARE REQUIRED FOR FOOD WASTE DISPOSERS |
| | CONNECTING TO GREASE INTERCEPTORS- SECTION 1003.3.2. |
| | |
| | 7) A1.6.4 & A1.6.5: ACCESSIBLE SHOWER: |
| | |
| | C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER |
| | SPRAY IN THE SHOWER- SECTION 608.5.2 FBC ACC. WHERE A |
| | SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER |
| | SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT |
| | TO THE SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM |
| | FROM THE SEAT WALL. DETAILS ON THE SHEETS SHOW THE |
| | CONTROLS ON THE SIDE WALL. |
| | |
| | E) FAILED SHOWER SEAT DIMENSIONS, HEIGHT, CLEARANCES |
| | AND EXTENSIONS AS OUTLINED IN SECTIONS 610.3 & 610.3.2. |
| | THE 2 FT. SHOWER SEAT DIMENSION EXCEEDS THE MAX 23 |
| | INCHES ALLOWED AS SHOWN IN FIGURE 610.3.2. PLEASE |
| | CORRECT THE DETAIL AND PROVIDE COMPLETE DIMENSIONS. |
| | |
| | 33) FAILED. PLEASE NOTE SEPARATE PERMIT APPLICATIONS |
| | AND PLANS ARE REQUIRED FOR THE POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER, BACKFLOW PREVENTER FOR THE CHILLER, |
| | IRRIGATION SYSTEM, FIRE LINE, FIRE LINE BACKFLOW |
| | PREVENTER, AND FIRE SPRINKLER SYSTEM. COMPLETE SETS OF |
| | PLANS AND SPECIFICATIONS ARE REQUIRED FOR REVIEW AND |
| | PERMIT ISSUANCE- SECTION 107.2.1 WPB. PROVIDE A LIST OF |
| | SEPARATE PERMITS ON THE PLANS INCLUDING THE RELOCATION |
| | OF BF PREVENTERS SHOWN ON C09. |
| | |
| | A) FAILED. BACKFLOW PREVENTERS: PLEASE NOTE THAT FL. |
| | LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE |
| | PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN |
| | ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB |
| | CODE OF ORDINANCES. THE DEVICES SHALL BE TESTED AND |
| | CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO |
| | FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE |
| | CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT |
| | 561-822-2210 FOR FURTHER INFORMATION. SEE COMMENT #33. |
| | |
| | B) FAILED. GREASE INTERCEPTOR: SUBMITTED PLANS SHALL |
| | INCLUDE GREASE WATER CALCULATIONS IN ACCORDANCE WITH |
| | SECTION 1003.3.4 FOR HYDROMECHANICAL INTERCEPTORS OR |
| | 1003.3.6 FOR GRAVITY TYPE INTERCEPTORS. MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION MANUALS SHALL ALSO BE |
| | SUBMITTED FOR REVIEW. SEE ADDED NOTES UNDER COMMENT #3 |
| | ABOVE. |
| | |
| | NEW COMMENT. |
| | |
| | 1) SHEET A1.64: THE DOOR TO THE WOMEN'S TLT. (P131) |
| | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORY- SECTION 603.2.3 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |