| Date |
Text |
| 2021-02-17 12:46:42 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120145 |
| | 2/16//2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW THAT HAVE PASSED ARE |
| | REMOVED. FAILED COMMENTS FROM THE 1ST REVIEW BELOW ARE |
| | MARKED FAILED WITH ADDITIONAL NOTES. ADDITIONAL NOTES |
| | HAVE BEEN ADDED TO SOME PASSED COMMENTS. |
| | |
| | 1) FAILED. SHEETS LS1.1 & LS1.2: PLEASE INCLUDE THE |
| | REQUIRED SERVICE SINKS IN THE PLUMBING FIXTURE |
| | CALCULATIONS- TABLE 403.1 FBC P. THREE SERVICE SINKS |
| | ARE REQUIRED FOR THE FACILITY. BASED ON TABLE 403.1 AND |
| | THE OCCUPANT LOAD IN PERCENTAGES: BUSINESS- 2.71 + |
| | ASSEMBLY- .194 = 2.904. MINIMUM 3 SERVICE SINKS. PLEASE |
| | REVISE THE PLANS ACCORDINGLY. |
| | |
| | 3) FAILED. A1.6.1 & P DRAWINGS: BASED ON THE SERVING |
| | KITCHEN PLAN IT APPEARS THAT A GREASE INTERCEPTOR MUST |
| | BE PROVIDED TO RECEIVE THE DRAINAGE FROM THE HOT FOOD |
| | WELL, DISHWASHER, FOOD WASTE DISPOSAL, AND ALL DIRECT |
| | OR INDIRECT WASTE RECEPTORS SERVING KITCHEN APPLIANCES |
| | AND EQUIPMENT THAT PRODUCE GREASE OR FAT-LADEN WASTE |
| | EFFLUENTS- SEE SECTION 1003.3.1 FBC P. CONCERNING THE |
| | FOOD WASTE DISPOSAL REFER TO SECTION 1003.3.2 FBC P AND |
| | PROVIDE A SOLIDS INTERCEPTOR TO SEPARATE THE DISCHARGE |
| | BEFORE CONNECTING TO THE INTERCEPTOR. BASED ON THE |
| | NARRATIVE RESPONSE TO COMMENTS, PLEASE PLACE A NOTE ON |
| | THE PLANS INDICATING NO FOOD PREPPARATION OR COOKING OF |
| | MEATS, FISH OR OTHER GREASE PRODUCING FOODS ALLOWED IN |
| | THE SERVING KITCHEN WITHOUT INSTALLATION OF A GREASE |
| | TRAP. |
| | |
| | 4) FAILED. A1.6.1, P0.0.1, & P2.1.1: THE SERVING |
| | KITCHEN SHOWS AN FD UNDER THE HOT FOOD WELL AND OTHER |
| | FLOOR DRAINS THAT ARE NOT INCLUDED IN THE FIXTURE |
| | SCHEDULE. CONCERNING THE FLOOR DRAIN SERVING THE FOOD |
| | WELL REFER TO SECTIONS 802.1 & 802.3: OTHER THAN HUB |
| | DRAINS THAT RECEIVE ONLY CLEAR-WATER WASTE AND |
| | STANDPIPES, A REMOVABLE STRAINER OR BASKET SHALL COVER |
| | THE OUTLET OF WASTE RECEPTORS. THE DISHWASHER SHALL |
| | ALSO DISCHARGE TO THE DRAINAGE SYSTEM THROUGH AN |
| | INDIRECT WASTE PIPE- PLEASE SECTIONS AND 802.3.1, |
| | 802.3.2 AND 427.1 FOR INDIRECT WASTE RECEPTOR |
| | COMPLIANCES. THE PLANS ALSO SHOW AN ICE MAKER AND |
| | BEVERAGE DISPENSERS IN THE KITCHEN WITH NO INDIRECT |
| | WASTE RECEPTORS BELOW THEM TO RECEIVE CONDENSATE |
| | DRAINAGE- SECTION 802.1 FBC P. PLEASE NOTE THAT |
| | CONDENSATE FROM COOLING COILS SHALL NOT DRAIN INTO THE |
| | CITY SANITARY SYSTEM- SECTION 90-126 WPB CODE OF |
| | ORDINANCES. CONCERNING THE ICE MAKER HOW IS THIS ISSUE |
| | BEING ADDRESSED? WILL THE UNIT PRODUCE CONDENSATE? |
| | |
| | 7) A1.6.4 & A1.6.5: ACCESSIBLE SHOWER, FBC ACC. SHEET |
| | A1.6.5 WITH SHOWER DETAILS WAS NOT UPLOADED PROPERLY |
| | AND CANNOT BE VIEWED. |
| | |
| | A) PASSED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE SHOWER- SECTION 608.2.1 |
| | B) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS- SECTION 608.3 AND 608.3.1. |
| | C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER |
| | SPRAY IN THE SHOWER- SECTION 608.5.1. |
| | D) FAILED. SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION |
| | 608.6. |
| | E) PASSED. SHOWER SEAT DIMENSIONS, HEIGHT, CLEARANCES |
| | AND EXTENSIONS AS OUTLINED IN SECTIONS 610.3 & 610.3.2. |
| | 9) FAILED. SINKS- P0.0.1: REFER TO SECTION 212.3 FBC |
| | ACC WHICH REQUIRES A MINIMUM OF 5%, BUT NO FEWER THAN |
| | ONE SINK OF EACH TYPE TO BE ACCESSIBLE. THIS WOULD |
| | INCLUDE THE L1, S1, S2, S3, S4, & S5 IN USE THROUGHOUT |
| | THE FACILITY. PLEASE DESIGNATE WHICH SINKS WILL BE MADE |
| | ACCESSIBLE BY SHOWING THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS AT EACH LOCATION ON THE ARCHITECTURAL AND |
| | PLUMBING DRAWINGS- SECTION 606.2. PROVIDE ELEVATION |
| | VIEWS FOR EACH ACCESSIBLE SINK SHOWING COMPLIANCE WITH |
| | SECTIONS 606.3, 306, 308, 309- HEIGHTS FROM FINISHED |
| | FLOORS, KNEE AND TOE CLEARANCES, REACH RANGE TO FAUCET |
| | CONTROLS, AND OPERABLE PARTS. THE ARCHITECTURAL FLOOR |
| | PLANS WERE NOT REVISED TO SHOW THE CLEAR FLOOR SPACE |
| | DIAGRAMS AND DIMENSIONS AND LOCATIONS OF THE ACCESSIBLE |
| | SINKS- LAV SINKS ARE SHOWN- SEE SHEETS A1.1.1, A1.1.2, |
| | & A1.1.3. SHEET A1.6.9 SHOWS A TYP. SINK AND A BASE |
| | CABINET W/ SINK DETAIL. PLEASE CLARIFY WHICH DETAIL |
| | APPLIES TO WHICH OF THE SINKS OF THE SHOWN ON THE |
| | PLANS. PLEASE NOTE I AM UNABLE TO VIEW REVISED SHEET |
| | A1.1.2 DUE TO AN ERROR IN THE UPLOADING PROCESS. |
| | |
| | 12) PASSED. P0.0.2: PROVIDE A PLUMBING DEVICE SCHEDULE |
| | INDICATING MAKES, MODEL NUMBERS AND LISTINGS FOR WATER |
| | HAMMER ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS, |
| | AND TRAP PRIMERS- SECTIONS 604.9, 607.2.1, 608.3 AND |
| | 1002.4.1.1 FBC P. DEFERRED SUBMITTALS REQUIRED TO BE |
| | ONSITE FOR INSPECTION- SEE NOTE FOR COMMENT 34. |
| | |
| | 15) FAILED. P0.0.1, P2.1.1, P4.1.1: INCLUDE THE WASHING |
| | MACHINE IN THE FIXTURE SCHEDULE AND INDICATE THE |
| | MACHINE SHALL DISCHARGE THROUGH AN INTERCEPTOR THAT IS |
| | PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE, |
| | REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE |
| | DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE, |
| | STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO |
| | THE PUBLIC SEWAGE SYSTEM- SECTION 1003.6 FBC P. PROVIDE |
| | AN EQUIPMENT SCHEDULE ON THE PLAN AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS TO VERIFY COMPLIANCE. |
| | PLACE A NOTE ON THE PLANS TO INDICATE FOR DOMESTIC |
| | PURPOSES, NOT FOR COMMERCIAL FACILITY USE. |
| | |
| | 16) PASSED. P2.1.1, P4.1.1, P4.1.2: SHOW TRAP PRIMER |
| | CONNECTIONS FOR EMERGENCY FLOOR DRAINS- SECTION |
| | 1004.2.1 FBC P. REVIEWER WILL PROVIDE A REDLINE NOTE ON |
| | APPROVED PLANS. |
| | |
| | 23) FAILED. P.2.2.1, P4.1.2: SHOW THE WATER SUPPLY |
| | PIPING TO THE WASHING MACHINE, DISHWASHER, BEVERAGE |
| | DISPENSER, AND ICE MAKER- TABLE 604.5 FBC P, AND |
| | SECTIONS 107.2.1, 107.3.5.1.3 WPB. SHOW THE REQUIRED |
| | WATER HAMMER ARRESTORS AND BACKFLOW PREVENTERS- |
| | SECTIONS 604.9 & 608.3 FBC P. WATER SUPPLY TO THE |
| | WASHING MACHINE, DISHWASHER, BEVERAGE DISPENSER, AND |
| | ICE MAKER NOT SHOWN. |
| | |
| | 24) FAILED. P.2.2.1, P.2.2.2, P2.2.3, P4.1.2: SHOW THE |
| | 3/4 IN. FIXTURE SUPPLY PIPES TO THE WATER CLOSETS AND |
| | URINALS- TABLE 604.5 FBC P. THE ISOMETRIC APPEARS TO |
| | SHOW 1/2 IN. CW LINES TO WC AND UR IN SOME LOCATIONS. |
| | FOR CLARIFICATION PLEASE SHOW THE SUPPLY PIPE SIZES OR |
| | ADD A NOTE. |
| | |
| | 26) FAILED. P2.2.1, P2.2.2, P2.2.3, P4.1.2, P5.1.1, |
| | P5.1.2: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO |
| | THE LAVATORIES- SECTION 416.5. SHOW MIXING VALVE |
| | LOCATIONS- SECTION 607.1.2 FBC P. MIXING VALVE |
| | LOCATIONS NOT SHOWN ON THE RISER. PLEASE SEE DEFINITONS |
| | OF TEMPERED WATER AND HOT WATER. IT APPEARS THAT |
| | TEMPERED WATER LINES ARE LABELED AS HW LINES. PLEASE |
| | CLARIFY HOW HW WILL BE SUPPLIED TO FIXTURES SUCH AS THE |
| | MOP SINKS AND WASHING MACHINE THAT REQUIRE HOT WATER- |
| | SECTION 607.1 FBC P. |
| | |
| | 28) FAILED. P0.0.2, P2.2.1, P4.1.2: BASED ON THE LEGEND |
| | IT APPEARS THE HOT WATER SYSTEM RETURN PIPE WILL BE A |
| | 1/2 IN. COLD WATER PIPE. IS THE PIPE SHOWN CORRECTLY? - |
| | SECTION 107.2.1 WPB AND SECTION C404.6.1 FBC EC.THE 1/2 |
| | IN. RETURN LINE TO EWH-1 IS STILL SHOWN AS A CW PIPE |
| | BASED ON THE LEGEND SYMBOLS ON P0.0.2. |
| | |
| | 33) FAILED. PLEASE NOTE SEPARATE PERMIT APPLICATIONS |
| | AND PLANS ARE REQUIRED FOR THE POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER, BACKFLOW PREVENTER FOR THE CHILLER, |
| | GREASE INTERCEPTOR, IRRIGATION SYSTEM, FIRE LINE, FIRE |
| | LINE BACKFLOW PREVENTER, AND FIRE SPRINKLER SYSTEM. |
| | COMPLETE SETS OF PLANS AND SPECIFICATIONS ARE REQUIRED |
| | FOR REVIEW AND PERMIT ISSUANCE- SECTION 107.2.1 WPB. |
| | PROVIDE A LIST OF SEPARATE PERMITS ON THE PLANS |
| | INCLUDING THE RELOCATION OF BF PREVENTERS SHOWN ON C09. |
| | A) FAILED. BACKFLOW PREVENTERS: PLEASE NOTE THAT FL. |
| | LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE |
| | PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN |
| | ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB |
| | CODE OF ORDINANCES. THE DEVICES SHALL BE TESTED AND |
| | CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO |
| | FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE |
| | CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT |
| | 561-822-2210 FOR FURTHER INFORMATION. SEE COMMENT #33. |
| | B) FAILED. GREASE INTERCEPTOR: SUBMITTED PLANS SHALL |
| | INCLUDE GREASE WATER CALCULATIONS IN ACCORDANCE WITH |
| | SECTION 1003.3.4 FOR HYDROMECHANICAL INTERCEPTORS OR |
| | 1003.3.6 FOR GRAVITY TYPE INTERCEPTORS. MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION MANUALS SHALL ALSO BE |
| | SUBMITTED FOR REVIEW. PROVIDE KITCHEN COOKING NOTE- SEE |
| | COMMENT #3. |
| | |
| | 34) PASSED. REQUIRED SUBMITTALS: MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALL MANUALS FOR THE WATER |
| | HEATERS, WASHING MACHINE, MIXING VALVES, RECIRCULATION |
| | PUMPS, SUMP PUMP, PIPE INSULATION, KITCHEN EQUIPMENT |
| | BACKFLOW PREVENTERS- SECTION 107.1 WPB. PLEASE ALL |
| | SUBMITTALS MAY BE DEFERRED IN ACCORDANCE WITH SECTION |
| | 107.3.4.1 WPB. PROVIDE A LIST OF DEFERRED SUBMITTALS TO |
| | BE REVIEWED AND APPROVAL BY THE DESIGN PROFESSIONALS OF |
| | RECORD, AND TO BE ONSITE AT TIME OF INSPECTION. |
| | |
| | NEW COMMENTS |
| | |
| | 1) SHEET A1.6.2 DETAIL 9: PLEASE CLARIFY IF AMBULATORY |
| | COMPARTMENTS ARE BEING INSTALLED. BASED ON SECTION |
| | 213.3.1 FBC ACC THEY ARE NOT REQUIRED, HOWEVER IF THE |
| | INTENTION IS TO PROVIDE ONE, PLEASE REVIEW SECTIONS |
| | 605.8.2, 604.8.2.1 & 604.8.2.2 FBC ACC AND CORRECT THE |
| | ARCHTECTURAL AND PLUMBING FLOOR PLANS. PLEASE PROVIDE |
| | GRAB BAR DETAILS- SECTION 604.8.2.3 FBC ACC. |
| | |
| | 2) A.1.8.1: THE ROOM FINISH SCHEDULE APPEARS TO SHOW |
| | EPOXY PAINTED GYPSUM WALLBOARD MATERIAL AS WALL FINISH |
| | FOR THE EVS ROOMS WHERE MOP SINKS ARE LOCATED. PLEASE |
| | NOTE WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE- SEE SECTION 1210.2.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |