Plan Review Notes
Plan Review Notes For Permit 20120141
Permit Number 20120141
Review Stop M
Sequence Number 5
Notes
Date Text
2021-07-21 08:04:121) I DO NOT SEE THAT A MECHANICAL PERMIT HAS BEEN
 ISSUED FOR THIS ADDRESS.
 2) THE DESIGNER OF THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS IS NOT A LICENSED ENGINEER NOR DOES HE
 HOLD THE MECHANICAL PERMIT TO INSTALL THE PROJECT. A
 LICENSED ENGINEER MUST SIGN AND SEAL THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS OR A LICENSED MECHANICAL
 CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL THIS
 PROJECT CAN PRINT AND THEN SIGN THEIR NAME ON THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. TIS MUST BE
 DONE BEFOR E THIS JOB WILL BE APPROVED IN PLAN REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  