| 2021-02-18 08:56:46 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE |
| | E4002.14, NEC 406.12 (A NOTE WILL SUFFICE) |
| | 2) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN |
| | EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL |
| | UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65 |
| | LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1 |
| | 3) ELECTRICAL WORK MUST COMPLY WITH NEC 2017, FBC RE |
| | 2020. (PLEASE ADD NOTE) |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |