Plan Review Notes
Plan Review Notes For Permit 20120109
Permit Number 20120109
Review Stop B
Sequence Number 3
Notes
Date Text
2021-03-10 11:14:44SFR REMODEL AND REPAIRS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK ROOFING
 = SHOWS A MAXIMUM DESIGN PRESSURE OF (-60) THE WIND
 PRESSURE FOR THE ROOF CLADDING IS NOT SHOWN ON THE
 DRAWINGS FBC TABLE R301.2(2) SHOWS THE PRESSURE FOR
 WIND ZONE 3 IS (-108.17 FOR EXPOSURE "C") ADDITIONAL
 ATTACHMENT DETAILS ARE REQUIRED. SEE NOTE NUMBER 9 ON
 PAGE 3 OF 74 - IF NEEDED PLEASE PROVIDE SIGNED AND
 SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY
 REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE
 PRODUCT APPROVAL.
  
  
  