| Plan Review Notes For Permit 20120109 |
| Permit Number |
20120109 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-03-10 11:14:44 | SFR REMODEL AND REPAIRS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK ROOFING | | | = SHOWS A MAXIMUM DESIGN PRESSURE OF (-60) THE WIND | | | PRESSURE FOR THE ROOF CLADDING IS NOT SHOWN ON THE | | | DRAWINGS FBC TABLE R301.2(2) SHOWS THE PRESSURE FOR | | | WIND ZONE 3 IS (-108.17 FOR EXPOSURE "C") ADDITIONAL | | | ATTACHMENT DETAILS ARE REQUIRED. SEE NOTE NUMBER 9 ON | | | PAGE 3 OF 74 - IF NEEDED PLEASE PROVIDE SIGNED AND | | | SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT | | | OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY | | | REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE | | | PRODUCT APPROVAL. | | | | | | | | | |
|