| Plan Review Notes For Permit 20120106 |
| Permit Number |
20120106 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-15 07:33:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PLANS NEED TO BE SIGNED AND SEALED BY AN ELECTRICAL | | | ENGINEER. | | | | | | F.S. 471.003 (H)?ANY ELECTRICAL, PLUMBING, | | | AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE | | | PRACTICE INCLUDES THE DESIGN AND FABRICATION OF | | | ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR MECHANICAL | | | SYSTEMS, RESPECTIVELY, WHICH SHE OR HE INSTALLS BY | | | VIRTUE OF A LICENSE ISSUED UNDER CHAPTER 489, UNDER | | | 1PART I OF CHAPTER 553, OR UNDER ANY SPECIAL ACT OR | | | ORDINANCE WHEN WORKING ON ANY CONSTRUCTION PROJECT | | | WHICH: | | | | | | REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600 AMPERES | | | (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM | | | OR 800 AMPERES (240 VOLTS) OR LESS ON A COMMERCIAL OR | | | INDUSTRIAL ELECTRICAL SYSTEM; | | | |
|